Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T06CM02423
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/01/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Justify allowable sq. footage because existing exceeds the allowable, or provide fire separation. Justify using formula 506.1 of IBC 2003. Look at old CofO for construction type. 2) Restroom for each sex needs to be provided see chapt. 29 table 2902.1. There is no justification in the IBC 2003 that allows you to decrease the occupant load for a space. 3) Clarify / justify occupancy for each tenant space. See table 1004.1.2. 4) Clarify accessibility for this facility see section 3409.6 exception 1. |