Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T06CM02419
Parcel: 10714376G

Review Status: Completed

Review Details: OTHER

Permit Number - T06CM02419
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM02418/9 4/26/06

1. Account for largest motor on panelboard schedule.
2. Show location of existing service.
3. Provide fault calculations demonstrating that relocated panels are within their fault current rating in their new location.
4. Retail Space Load Calculation adds Strip Heaters and Indoor Fan motors. Does not appear to be correspondence to this load on panel schedules.
5. Panel schedules have Point-of-Use Water Heaters. Do not have correspondence on Retail Space Load Calculation.
6. Retail Space Load Calculation accounts for only 7 General Use Receptacles. There are 10 per unit.