Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T06CM02419
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/04/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06CM02418/9 4/26/06 1. Account for largest motor on panelboard schedule. 2. Show location of existing service. 3. Provide fault calculations demonstrating that relocated panels are within their fault current rating in their new location. 4. Retail Space Load Calculation adds Strip Heaters and Indoor Fan motors. Does not appear to be correspondence to this load on panel schedules. 5. Panel schedules have Point-of-Use Water Heaters. Do not have correspondence on Retail Space Load Calculation. 6. Retail Space Load Calculation accounts for only 7 General Use Receptacles. There are 10 per unit. |