Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM02418
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/26/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/26/2006 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 04/26/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM02418 4/26/06 1. Since occupant shall have access to all overcurrent protective devices, new receptacles shall not be powered from adjacent suite. 2. It appears that the new receptacle on the opposite wall is intended for Ckt 2, not 4. 3. Account for largest motor on panelboard schedule. Adding 25% of the AC unit, it appears that Phase A is overloaded. 4. Show location of existing service and panels on scaled drawing. 5. Provide fault calculations demonstrating that relocated panels are within their fault current rating in their new location. |
| 05/01/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 05/01/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 05/01/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/01/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/01/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/02/2006 | GERRY KOZIOL | WWM | REVIEW | Approved |