Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
04/26/2006 JASON GREEN ENGINEERING REVIEW Approved
04/26/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM02418 4/26/06

1. Since occupant shall have access to all overcurrent protective devices, new receptacles shall not be powered from adjacent suite.
2. It appears that the new receptacle on the opposite wall is intended for Ckt 2, not 4.
3. Account for largest motor on panelboard schedule. Adding 25% of the AC unit, it appears that Phase A is overloaded.
4. Show location of existing service and panels on scaled drawing.
5. Provide fault calculations demonstrating that relocated panels are within their fault current rating in their new location.
05/01/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/01/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
05/01/2006 ROBERT SHERRY WATER REVIEW Approved
05/01/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/01/2006 MARTIN BROWN FIRE REVIEW Approved
05/02/2006 GERRY KOZIOL WWM REVIEW Approved