Permit Number: T06CM02414
Parcel: 12213055E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM02414
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/25/2006 HEATHER THRALL ZONING REVIEW Approved
04/25/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved Provide ventilation calculations per Sections 403.3 and 403.2, IMC 2003.
04/25/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/25/2006 ROBERT SHERRY WATER REVIEW Approved
04/25/2006 MARTIN BROWN FIRE REVIEW Approved
04/25/2006 RSHERRY1 WWM REVIEW Passed
04/25/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
04/26/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM02414 4/25/06

1. Receptacles shall be counted at no less than 180 VA per outlet. Correct this on Ckts A-12, B-5, B-7, and all others which apply. (This is an incomplete review for Power.)
2. Lighting Plan has lights on Ckt B-8. On the Panel Schedule this circuit powers receptacles.
3. Copy on line diagram not legible.
4. Provide breaker sizes on panel schedules for all new loads.
5. Specify conduit and conductor size and type.
04/26/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved