Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/25/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
04/25/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | Provide ventilation calculations per Sections 403.3 and 403.2, IMC 2003. |
04/25/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
04/25/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/25/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
04/25/2006 | RSHERRY1 | WWM | REVIEW | Passed | |
04/25/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
04/26/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06CM02414 4/25/06 1. Receptacles shall be counted at no less than 180 VA per outlet. Correct this on Ckts A-12, B-5, B-7, and all others which apply. (This is an incomplete review for Power.) 2. Lighting Plan has lights on Ckt B-8. On the Panel Schedule this circuit powers receptacles. 3. Copy on line diagram not legible. 4. Provide breaker sizes on panel schedules for all new loads. 5. Specify conduit and conductor size and type. |
04/26/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved |