Permit Number: T06CM02391
Parcel: 10707005K

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T06CM02391
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2007 ROBERT SHERRY WATER REVIEW Denied 1. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
2. Revise the site drawing to show the size of both the water meter and indicate the design water demand. Reference Section 103.2.3, UPC 2003.
04/26/2007 DAVE MANN FIRE REVIEW Approved
04/30/2007 GERRY KOZIOL WWM REVIEW Denied needs WW/IWC review- Tom Tomchak 579-5771
05/01/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied An approved site plan and floodplain use permit is required prior to building plan approval.
05/10/2007 TERRY STEVENS ZONING REVIEW Denied 05/14/07

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments regarding T06CM02391 and T06CM05693:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming.
06/02/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/12/2007 CINDY AGUILAR APPROVAL SHELF Completed
06/12/2007 CINDY AGUILAR OUT TO CUSTOMER Completed