Permit Number: T06CM02338
Parcel: 12709012C

Review Status: Completed

Review Details: OTHER

Permit Number - T06CM02338
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide structural calculations and details to show that the installation of the A/C unit will not adversely impact the building structure. Reference Sections 106.3.1 and 302.1, IMC 2003.
08/15/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved S1. PROVIDE STRUCTURAL CALCULATIONS AND DETAILS FOR SUPPORT OF SUSPENDED MECH UNITS. SEE SECTION 1603 AND 1606.2.