Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T06CM02327
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/06/2006 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 11/22/2006 | DANIEL RUSCH | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN REVIEW COMMENTS for Activity # T06CM02327 Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration. As of 9-02-04 the City of Tucson has adopted the 2003 IRC with the exception of the plumbing portion which has been replaced with the 2003 UPC with amendments. All plans should reference these codes. See this site for all adopted amendments: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html All code references to the International Residential Code shall be changed from 2000 to 2003 with appropriate paragraph references: Sheet A-1, Section 6100 note 6; Section 6200 note 1 & 5. Sheet A-2, window note 5. SITE PLAN: 1. Indicate the location of gas, water, electric and sewer or septic line on the property, from property line to building. Provide the location of utility meters. 2. Show the water pipe size from the meter to the building. Show the point of connection for the proposed branch. The pipe must be sized for the calculated load, 2003 UPC 610.1. FOUNDATION PLANS: 1. Epoxy connections require special inspections. If used, a special inspection request must be included with the permit application. FLOOR PLANS: 1. Show the garage floor direction of slope, R309.3. STRUCTURAL PLANS: 1. Provide manufacturer's calculations and data for pre-fabricated trusses (Detail 2/S-2), R802.10.2, or note the requirement for deferred submittal approval prior to installation. ELEVATIONS: 1. Note and specify appropriate (two-layer) underlayment material for the low-slope (2:12 to 4:12) asphalt shingle roof, R905.2.7. 2. Note and specify all roof slopes appropriate with selected material, R901.1. SECTIONS - DETAILS - MISC. NOTES: 1. Calculate the attic ventilation area using the correct attic area in compliance with R806.2. Note only 80% of the required ventilating area may be provided by ridge or gable vents when applying the reduced area calculation. Show the amount of eave vents needed to comply. 2. Show a minimum 1" ventilation clearance between ceiling insulation and roof sheathing (Detail 2/S-2), R806.3. This may be accomplished w/ baffles. PLUMBING PLANS: 1. The City of Tucson has adopted the 2003 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). The plans should reference this code. Correct sheet MP-1, Plumbing note. 2. Provide the total fixture unit demand for the entire property per 2003 UPC Table 6-4. Water closet: 2.5 x _____ = _____ Lav: 1.0 x _____ = _____ Bathtub: 4.0 x _____ = _____ Shower: 2.0 x _____ = _____ Kitchen sink: 1.5 x _____ = _____ Dishwasher: 1.5 x _____ = _____ Bar sink: 1.0 x _____ = _____ Laundry sink: 1.5 x _____ = _____ Clothes washer: 4.0 x _____ = _____ Ice maker: 0.5 x _____ = _____ Hose bibb (first): 2.5 x _____ = _____ Hose bibb (additional): 1.0 x _____ = _____ 3. Provide the total fixture unit demand for the entire property per 2003 UPC Table 6-4, and determine the supply line diameter from Table 6-5 assuming 46 to 60 psi, if the water pipe serves both the existing and proposed fixtures. MECHANICAL PLANS: 1. Note on plans: Mechanical shall comply with 2003 IRC chapters 12 - 24. Correct sheet MP-1, Mechanical note 1. 2. Show dryer vent size and location, M1501. ELECTRICAL PLANS: 1. Note on plan that all electrical work shall comply with 2003 IRC chapters 33 - 42. Change sheet E-1, note 3 from Pima County to City of Tucson. 2. Provide equipment rated for 22,000 AIC short circuit protection, 2006 Edition of Electric Service Requirements TEP SR-510. 3. Use Table E3602.13 for sizing 15, 20 & 30 AMP branch circuit conductors. Change conductors to #10 for circuit A5/7. 4. Use Table E3605.1, 60 degree C column, for sizing branch circuits and conductors rated at 100 AMP or less, E3605.4.1. Change conductors to #6 for circuit A21/23. 5. Provide appropriate feeder conductor quantity and sizes for the AC disconnect on the Service Diagram, E3605. 6. Note that an arc-fault circuit interrupter shall protect bedroom outlets including receptacles, lights and smoke detectors, E3802.11. 7. Provide a note indicating only approved outlet boxes shall be used for ceiling fans, E4001.6. 8. Show locations of smoke detectors, R313. Note that all smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup. This includes existing bedrooms with attic space, R313.1.1. 9. Smoke alarms are required outside each separate sleeping area, R313.1.2. INTERNATIONAL ENERGY CONSERVATION CODE: 1. Tucson is in climate zone 4B, 2100 HDD, IRC chapter 11, local amendment. The simplified prescribed energy values for glazing U=0.65, ceiling R=30 and walls R=13 complies with 2003 IECC energy requirements, if glazing does not exceed 15% of exterior wall area. Show these values, or provide energy calculations per the 2003 IECC for compliance validations. Select the climate zone 4B, Pima County < 4000 ft, 2100 HDD if using REScheck. http://www.energycodes.gov/rescheck/ 2. Show the "U" factors of the windows and doors on the plans as well as the solar heat gain coefficient SHGC minimum value of 0.40. If you have any questions, please contact your assigned plans examiner Ken Van Karsen at 791-5550, extension 1112. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/28/2006 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 11/28/2006 | SUE REEVES | REJECT SHELF | Completed |