Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T06CM02311
Parcel: 11705074A

Address:
300 E 7TH ST

Review Status: Completed

Review Details: OTHER

Permit Number - T06CM02311
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM02311 4/21/06
THIS IS AN INCOMPLETE REVIEW. THE ITEMS BELOW NEED TO BE SATISFIED BEFORE OK TO SUBMIT FOR ELECTRICAL REVIEW.

1. Provide cut sheets for extraction equipment.
2. Demonstrate that the composition of the vapors is such that they do not exceed 25% of LEL. Otherwise, plans have to be prepared by a Registered Electrical Engineer.
04/26/2006 JASON GREEN ENGINEERING REVIEW Needs Review
04/26/2006 AOLIVO1 ZONING REVIEW Needs Review