Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM02311 4/21/06
THIS IS AN INCOMPLETE REVIEW. THE ITEMS BELOW NEED TO BE SATISFIED BEFORE OK TO SUBMIT FOR ELECTRICAL REVIEW.

1. Provide cut sheets for extraction equipment.
2. Demonstrate that the composition of the vapors is such that they do not exceed 25% of LEL. Otherwise, plans have to be prepared by a Registered Electrical Engineer.
04/26/2006 JASON GREEN ENGINEERING REVIEW Needs Review
04/26/2006 AOLIVO1 ZONING REVIEW Needs Review