Permit Number: T06CM02285
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM02285
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) PLEASE PROVIDE STRUCTURAL CALCULATIONS FOR THE LIGHT POLE BASES PER SECTION 106.1.1 OF THE 2003 IBC.

2) PLEASE COORDINATE THE OUTDOOR LIGHTING INFORMATION BETWEEN THE SCHEDULE, THE LIGHTING PLAN, AND SHEET A-1 PER SECTION 106.1.1 OF THE 2003 IBC. THE CURRENT SUBMITTAL OF SHEET A-1 INDICATES 14 EXISTING WALL MOUNTED LIGHTS, BUT THE SCHEDULE ONLY DENOTES 3 AND BOTH SHEETS A-1 AND THE LIGHTING PLAN INDICATE 11 POLE MOUNTED FIXTURES, BUT THE SCHEDULE ONLY LISTS 9.
05/17/2007 CHRIS KIEL (WILDAN) ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/05/2007 CINDY AGUILAR OUT TO CUSTOMER Completed
06/05/2007 CINDY AGUILAR REJECT SHELF Completed