Permit Number: T06CM02274
Parcel: 108214430

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM02274
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
04/20/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
04/20/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM02274 4/20/06

1. Please correct load tabulations on panels, to give Owner better sense of spare capacity. Panel XR lighting loads at 125% appear to be 6660 VA, not 5328; receptacles 7380 VA, not 5580. Panel A Ckts 9 and 11 undercounted, receptacle total 7920 VA not 6300; fixed loads 6000 VA not 5000.
04/20/2006 MARTIN BROWN FIRE REVIEW Approved
04/21/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/21/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide plumbing design.
04/21/2006 ROBERT SHERRY WATER REVIEW Approved
04/21/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
04/25/2006 DROBEY1 WWM REVIEW Needs Review