Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM02274
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/20/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
04/20/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
04/20/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM02274 4/20/06 1. Please correct load tabulations on panels, to give Owner better sense of spare capacity. Panel XR lighting loads at 125% appear to be 6660 VA, not 5328; receptacles 7380 VA, not 5580. Panel A Ckts 9 and 11 undercounted, receptacle total 7920 VA not 6300; fixed loads 6000 VA not 5000. |
04/20/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
04/21/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
04/21/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide plumbing design. |
04/21/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/21/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/25/2006 | DROBEY1 | WWM | REVIEW | Needs Review |