Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM02249
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/11/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) CLARIFY / JUSTIFY ON BUILDING PLAN OTHER TENANT OCCUPANCY FOR VERIFICATION OF MOST RESTRICTIVE USE. BUILDING FLOOR PLAN SHALL BE PROVIDED CLARIFYING OTHER OCCUPANCIES OF BUILDING. PROVIDE CODE ANALYSIS FOR BOTH SUITES. 2) PROVIDE DIMENSIONS FOR SHOWER PER ANSI A117.1 2003. GRAB BARS ARE REQUIRED FOR THE SHOWER. PLEASE SPECIFY SHOWER PER SECTION 608. 3) IF YOUR PROVIDING NEW FACILITIES IN A RESTROOM. ACCESS INTO THE RESTROOM MUST FIRST BE ADDRESSED. SEE SECTION 404.2.3.1. 4)DOOR HAS BEEN CLOSED IN THERFORE NO ONE IS ABLE TO GET INSIDE THE RESTROOM. SEE NOTATION FOR NEW FRAMING. |
| 05/11/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 05/11/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM02249 5/11/06 1. Specify overcurrent protection and conductor size for WH-1. It is not clear on the plans if the existing circuit is sufficient. 2. Provide power for EF-1E, specified on Sheet M1.1. 3. Provide panel schedule. |
| 05/11/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/16/2006 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 05/16/2006 | CAGUILA1 | ENGINEERING | REVIEW | Needs Review |