Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM02248
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/19/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 04/19/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM02248 4/19/06 1. Provide power for WH-1, specified on Sheet P1.1. 2. Provide power for EF-1E, specified on Sheet M1.1. 3. Provide panel schedule. |
| 04/19/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) CITY OF TUCSON DOES NOT BANK BUDGET SPENT TOWARDS ACCESSIBILITY. IT IS CONSIDERED FOR EACH PERMIT ONLY UNTIL FULLY COMPLIANT. 2) CLARIFY / JUSTIFY ON BUILDING PLAN OTHER TENANT OCCUPANCY FOR VERIFICATION OF MOST RESTRICTIVE USE. |
| 04/20/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2003. |
| 04/20/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide information to show how the outlet temperature of the hot water is to be limited to 110 degrees at the lavatory. Reference Section 804.3, IECC 2003. 2. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference Section 804.4, IECC 2003. 3. If the specified water heater is not supplied with integral heat traps, provide 0.5" of insulation with a maximum conductivity of 0.27 btu per inch/h °F on the first 8 feet of supply piping. Reference Section 804.4, IECC 2003. |
| 04/20/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/20/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/11/2006 | AOLIVO1 | WWM | REVIEW | Needs Review | |
| 05/11/2006 | AOLIVO1 | ENGINEERING | REVIEW | Needs Review |