Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2006 HEATHER THRALL ZONING REVIEW Approved
04/19/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM02248 4/19/06

1. Provide power for WH-1, specified on Sheet P1.1.
2. Provide power for EF-1E, specified on Sheet M1.1.
3. Provide panel schedule.
04/19/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) CITY OF TUCSON DOES NOT BANK BUDGET SPENT TOWARDS ACCESSIBILITY. IT IS CONSIDERED FOR EACH PERMIT ONLY UNTIL FULLY COMPLIANT.
2) CLARIFY / JUSTIFY ON BUILDING PLAN OTHER TENANT OCCUPANCY FOR VERIFICATION OF MOST RESTRICTIVE USE.
04/20/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2003.
04/20/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide information to show how the outlet temperature of the hot water is to be limited to 110 degrees at the lavatory. Reference Section 804.3, IECC 2003.
2. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference Section 804.4, IECC 2003.
3. If the specified water heater is not supplied with integral heat traps, provide 0.5" of insulation with a maximum conductivity of 0.27 btu per inch/h °F on the first 8 feet of supply piping. Reference Section 804.4, IECC 2003.
04/20/2006 ROBERT SHERRY WATER REVIEW Approved
04/20/2006 MARTIN BROWN FIRE REVIEW Approved
05/11/2006 AOLIVO1 WWM REVIEW Needs Review
05/11/2006 AOLIVO1 ENGINEERING REVIEW Needs Review