Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T06CM02246
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/02/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/02/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Clarify how and where the thermostatic valve (keynote 8) is to be installed and specify the product to be used. |
| 08/03/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM02246 8/3/06 1. Provide fault calculations for AFC at panel, given the new service. 2. Specify that the N-G bond at the new service entrance shall be no smaller than 350 MCM. Reference NEC 250.102 (C). |
| 08/08/2006 | GBONILL1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/08/2006 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |