Permit Number: T06CM02246
Parcel: 112062350

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T06CM02246
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/02/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify how and where the thermostatic valve (keynote 8) is to be installed and specify the product to be used.
08/03/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM02246 8/3/06

1. Provide fault calculations for AFC at panel, given the new service.
2. Specify that the N-G bond at the new service entrance shall be no smaller than 350 MCM. Reference NEC 250.102 (C).
08/08/2006 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/08/2006 GERARDO BONILLA OUT TO CUSTOMER Completed