Permit Number: T06CM02246
Parcel: 112062350

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM02246
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2006 TERRY STEVENS ZONING REVIEW Approved
04/19/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
04/19/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM02246 4/19/06

1. Please eliminate the #2 GND between the weatherhead and the gutter as a redundant path.
2. Provide power for the recirculating pump specified on Sheet P-2.
3. Circuit DD-17 appears twice. Please clarify intent.
04/19/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE VALUATION FOR THIS PROJECT.
2) A BUILDING APPEAL WILL NEED TO BE FILED TO JUSTIFY ONLY ONE RESTROOM WITH A REDUCED OCCUPANT LOAD.
04/20/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/20/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/20/2006 ROBERT SHERRY WATER REVIEW Approved
04/20/2006 MARTIN BROWN FIRE REVIEW Approved
04/25/2006 GERRY KOZIOL WWM REVIEW Approved