Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM02246
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/19/2006 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 04/19/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
| 04/19/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM02246 4/19/06 1. Please eliminate the #2 GND between the weatherhead and the gutter as a redundant path. 2. Provide power for the recirculating pump specified on Sheet P-2. 3. Circuit DD-17 appears twice. Please clarify intent. |
| 04/19/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE VALUATION FOR THIS PROJECT. 2) A BUILDING APPEAL WILL NEED TO BE FILED TO JUSTIFY ONLY ONE RESTROOM WITH A REDUCED OCCUPANT LOAD. |
| 04/20/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/20/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 04/20/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/20/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/25/2006 | GERRY KOZIOL | WWM | REVIEW | Approved |