Permit Number: T06CM02191
Parcel: 12101103E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM02191
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/17/2006 TERRY STEVENS ZONING REVIEW Approved
04/17/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/17/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
04/17/2006 ROBERT SHERRY WATER REVIEW Approved
04/17/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied S1. ADDRESS ACCESSIBILITY SHOW ON DRAWINGS WHERE 20% OF PROJECT VALUATION IS SPENT ON ACCESSIBILITY.
S2. CLARIFY FINISHES IN TOILET ROOM ie: WAINSCOT?
S3. CLARIFY TOILET ROOM :
1. PROVIDE LARGER FLOOR PLAN, EXPLAIN ACCESSIBILITY.
2. PROVIDE CROSS-SECTION THROUGH LAV SHOWING DEPTHS FOR KNEE AND TOE CLEARANCES.
S4. PROVIDE 1/8 INCH MINIMUM LETTER SIZE, REF A1 AND A2.
04/17/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
04/17/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the plumbing riser diagram for rooms 112 and 113 to include the existing sink.
2. Provide an upper terminal cleanout for P-1 in room 113. Reference Section 707.4, UPC 2003.
3. Provide an upper terminal cleanout for P-4. Reference Section 707.4, UPC 2003.
4. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
5. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, and valves. Reference Sections 103.2.3, 605.5, and 608.3 UPC 2003.
6. Adjust the size of the fonts on the drawings to a minimum of 1/8".
04/17/2006 MARTIN BROWN FIRE REVIEW Approved
04/25/2006 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/25/2006 DELMA ROBEY OUT TO CUSTOMER Completed