Permit Number: T06CM02179
Parcel: 13615378B

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T06CM02179
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2006 MARTIN BROWN FIRE REVIEW Denied Need more details regarding layout of future restaurant.
Fire sprinklers may be required, if occupant load is 100 or more.
08/22/2006 ROBERT SHERRY WATER REVIEW Approved
08/23/2006 PAUL MACHADO ENGINEERING REVIEW Denied To: Brian Short DATE: August 23, 2006
BRS Architecture 1313 S Copias Way
Tucson, Arizona 85713

SUBJECT: Golf Links Comm. Bldg., 7755 E Golf Links Rd.
Site plan T06CM02179 (Second Review)
T14S, R15E, Section 29

RESUBMITTAL REQUIRED: Site Plan and Drainage Report.

The Site Plan (SP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP.
2. During the first review, I did not notice that sidewalks will be required along the entire length of all street frontages. This includes but not limited to upgrading the existings W/C ramps to meet current code per D.S. 3-01.2.4.3.A.
3. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations have been designed and located will suffice. Although the scuppers have been added, it appears that the scuppers may not be able to drain into the P.A.A.L. because of the handicap ramp.

Drainage Report:
1. The DR has been accepted for site plan purposes only. Final acceptance will be given at the grading plan stage.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax, 7755 E Golf Links Rd. site2
08/28/2006 GERRY KOZIOL WWM REVIEW Denied cannot connect 6" HCS to 8" public sewer- need to connect to a manhole (new or exsisting) needs 8th floor review, 5th floor permit
09/08/2006 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 7755 E. Golflinks Rd. New Commerical Strip Ctr.
T06CM02179
Building Plan (1st Review)

TRANSMITTAL DATE: September 08, 2006

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please call Steve Shields,
(520) 791-5608 ext. 1180.

C:\planning\grading\t06cm02179.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
09/11/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/12/2006 JMORALE1 OUT TO CUSTOMER Completed
09/12/2006 SUE REEVES REJECT SHELF Completed