Permit Number: T06CM02154
Parcel: 118122380

Address:
249 E 25TH ST

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T06CM02154
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2006 PETER MCLAUGHLIN ZONING REVIEW Approved
07/20/2006 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. A street landscape border, per Sec. 3.7.2.4 of the LUC, is a landscape area with a minimum width of ten (10) feet, running the full length of the street property line(s) bounding the site(s) except for points of ingress-egress. Landscape borders are required for 249 E. 25th St. including 4th Ave. street frontage.

2. Include with re-submittal any variance documentation. Indicate on the lower right hand corner of the site and landscape plans, the variance case number, date of approval, and any conditions imposed.
08/11/2006 JASON GREEN ENGINEERING REVIEW Approved DATE: August 11, 2006
SUBJECT: Proposed Coffee Shop- Site Plan Review
TO: Steve Gregor
LOCATION: 249 E 25th Street, T14S R13E Sec24, Ward 5
REVIEWERS: Jason Green, CFM
ACTIVITY: T06CM02154


SUMMARY: Engineering Division of Development Services Department has received and reviewed the re-submitted site plan and Hydrology Report. The Hydrology Report was reviewed for site plan purpose only. Engineering Division recommends approval of the site at this time.


For any questions call me at 791-5550, extension 1189.


Jason Green, CFM
Senior Engineer Associate
Engineering Division
Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
08/16/2006 BETH GRANT OUT TO CUSTOMER Completed
08/16/2006 SUE REEVES REJECT SHELF Completed