Permit Number: T06CM02118
Parcel: 12009308A

Address:
4823 S 6TH AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM02118
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/24/2006 MARTIN BROWN FIRE REVIEW Approved
05/08/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/08/2006 RSHERRY1 WWM REVIEW Passed
05/08/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
05/08/2006 ROBERT SHERRY WATER REVIEW Approved
05/11/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
05/18/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 5/19/06
ACTIVITY NUMBER: T06CM02118
PROJECT NAME: Tucson Rodeo Parade - Metal Building Maintenance
PROJECT ADDRESS: 4823 S. 6th Ave
ARCHITECT / ENGINEER: Structural Concepts Inc.
PROJECT REVIEWER: Christy Foreman


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) 1997 Uniform Administrative Code - section 302.5 Inspection and Observation Program. When special inspection is required by Section 306, the architect or engineer of record shall prepare an inspection program which shall be submitted to the building official for approval prior to issuance of the building permit. The inspection program shall designate the portions of the work to have special inspection, the name or names of the individuals or firms who are to perform the special inspections and indicate the duties of the special inspectors.

The special inspector shall be employed by the owner , the engineer or architect of record, or an agent of the owner, but not the contractor or any other person responsible for the work.

When structural observation is required by Section 307, the inspection program shall name the individuals or firms who are to perform structural observation and describe the stages of construction at which structural observation is to occur.

The inspection program shall include samples of inspection reports and provide time limits for submission of reports.


2) Justify 20% cost of construction being spent toward accessibility requirements per code section 3409.6 IBC 2003. Provide itemized breakdown of costs for items on the drawings.
3) Site plan needs to be dimensioned to clarify code analysis. Distance between buildings etc.
4) Clarify Occupancy - Storage or Museum?
5) Clarify fire separation between building H & I.

6) Design and structural calculations will need to be provided before a permit can be issued for all structural items that are being replaced.
7) Clarify location of restroom facilities for this location.
8) Lavatories 1/100 per table 2902.1 - SP-1 specifies 1/1000.
05/19/2006 MARTY DUPONT ADA REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/12/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
01/12/2007 SUE REEVES REJECT SHELF Completed