Permit Number: T06CM02097
Parcel: 128040960

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T06CM02097
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2006 DANIEL RUSCH BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS for Activity # T06CM02097

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, model energy and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.


Provide a note for: Underground facility tracer wires per DSD Memo, 10/24/2005.


FOUNDATION PLANS:

1. Show the minimum 12" footing depth below undisturbed soil for F1 & F3, R403.1.4.
2. Show compliance with termite treatment specified by R320, as amended.

STRUCTURAL PLANS:

1. Identify the beam and supports parallel to the fireplace face, sheet S1.2.
2. Provide the size for the post shown on detail #5/S1.4.
3. Correct rebar lap to 40 diameters, detail #6/S1.3.

ELEVATIONS:

1. Specify a vapor barrier on detail1/S1.3, R703.2.

SECTIONS - DETAILS - MISC. NOTES:

1. Correct the detail reference on keynote #2/A3.1.
2. Ceiling gypsum board shall be either 5/8" or ½" sag resistant when applied to 24" o/c framing, IRC table R702.3.5 footnote d. Clarify keynote #7/S1.2 and detail #6 & 7/A5.1.
3. Roof ventilation is not appropriate with full insulation within ceiling cavity, R806.3. Clarify detail #2/A3.1.

PLUMBING PLANS:

1. Revise the plumbing fixture schedule to represent the plan per 2003 UPC Table 6-4.

MECHANICAL PLANS:

1. Note on plans if H/C #1 & 2 are existing or new. If new, show location, gas connection schedule with gas piping and return air duct information.
2. Show plumbing vents (VTR) within acceptable distances from traps (maximum 6' for water closets), UPC Table 10-1.

ELECTRICAL PLANS:

1. Show locations of smoke detectors, R313. Note that all smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup. When ceiling finish materials are removed in existing construction, existing bedrooms shall be in compliance. When ceiling finish materials are not removed, existing bedrooms shall be equipped with battery operated smoke detectors, R313.1.1.
2. Smoke alarms are required outside each separate sleeping area R313.1.2.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. R-30 batt insulation will not provide rated value in a 2" x 8" space. Show compliance.
2. Provide the simplified prescribed energy values for glazing U=0.65, ceiling R=30 and walls R=13, or provide energy calculations per the 2003 IECC w/ local amendments for compliance validations. If using REScheck select the climate zone 4B, Pima County < 4000 ft, 2100 HDD on the web version. http://www.energycodes.gov/rescheck/ The solar heat gain coefficient SHGC should have a minimum value of 0.40.


If you have any questions, please contact your assigned plans examiner Ken Van Karsen at 791-5550, extension 1112.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/26/2006 GBONILL1 OUT TO CUSTOMER Completed
04/26/2006 SUE REEVES REJECT SHELF Completed