Permit Number: T06CM02095
Parcel: 13711425D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM02095
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/12/2006 HEATHER THRALL ZONING REVIEW Approved
04/12/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
04/13/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM02095 4/13/06

1. It appears that Panel P1 Phase C is overloaded. It appears that there are 230A on this 225 A panel.
04/13/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify the scope of mechanical work in this project.
04/13/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the new hand washing sink is to be plumbed (water and waste).
2. Indirect waste lines less than 5 feet long do not require a trap.
04/14/2006 AOLIVO1 WATER REVIEW Needs Review
04/14/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved 1) IT APPEARS OCCUPANT LOAD IS INCORRECT. MERCANTILE = 1/30SQ.FT STORAGE AREA = 1/300 SQ.FT
PLEASE CORRECT.
04/14/2006 AOLIVO1 WWM REVIEW Needs Review
04/14/2006 AOLIVO1 FIRE REVIEW Needs Review