Permit Number: T06CM02094
Parcel: 112032850

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM02094
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/12/2006 HEATHER THRALL ZONING REVIEW Approved
04/12/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
04/13/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
04/13/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/13/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Indirect waste lines greater than 15 feet require a vented trap, not connected to any sanitary vents.
2. Show how the relocated han sink is to be plumbed.
3. Clarify the work to be done with regards to Keynotes 17 and 18, sheet A2.
04/13/2006 ROBERT SHERRY WATER REVIEW Approved
04/14/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) SHT A-1 JUSTIFICATION FOR HOW 20% COST OF CONSTRUCTION IS BEING SPENT TOWARDS ACCESSIBILTY IS MISSING.
2)OCCUPANT LOADS NEED TO BE RECALCULATED FOR MERCANTILE 1/30 AND STORAGE 1/300
04/14/2006 AOLIVO1 WWM REVIEW Needs Review
04/14/2006 AOLIVO1 FIRE REVIEW Needs Review