Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM02094
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/12/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 04/12/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 04/13/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 04/13/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/13/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Indirect waste lines greater than 15 feet require a vented trap, not connected to any sanitary vents. 2. Show how the relocated han sink is to be plumbed. 3. Clarify the work to be done with regards to Keynotes 17 and 18, sheet A2. |
| 04/13/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/14/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) SHT A-1 JUSTIFICATION FOR HOW 20% COST OF CONSTRUCTION IS BEING SPENT TOWARDS ACCESSIBILTY IS MISSING. 2)OCCUPANT LOADS NEED TO BE RECALCULATED FOR MERCANTILE 1/30 AND STORAGE 1/300 |
| 04/14/2006 | AOLIVO1 | WWM | REVIEW | Needs Review | |
| 04/14/2006 | AOLIVO1 | FIRE | REVIEW | Needs Review |