Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM02074
Parcel: 12209003A

Address:
3915 E PIMA ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM02074
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2006 MARTIN BROWN FIRE REVIEW Approved
04/11/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
04/11/2006 SUZANNE BOHNET ENGINEERING REVIEW Needs Review
04/11/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
04/13/2006 ROBERT SHERRY WATER REVIEW Approved
04/13/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how the ventilation of the space complies to the requirements of Section 403.3, IMC 2003.
04/13/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the size the waste line for the water closet from 2" to at least 3".
2. The trap for the water closet is located inside the water closet.
3. Show how the existing lavatory is to be re-plumbed.
4. Show how the new water piping relates to the existing piping.
5. Show how the water piping was sized (e.g. Appendix A, UPC 2003).
6. Clarify which water pipe is hot and which is cold.
7. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
04/17/2006 SREEVES1 ZONING REVIEW Needs Review
04/17/2006 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/17/2006 SUE REEVES OUT TO CUSTOMER Completed