Permit Number: T06CM01995
Parcel: Unknown

Address:
3851 S 6TH AV

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T06CM01995
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/19/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Special Inspection certification form for epoxy bolts needs to be submitted before the permit can be issued.
2) Provide floor plan and exterior elevation to locate scope of work. Dimension location of new work on existing building.
3) Provide elevation and section showing specification for installation of tube steel column per the structural calculations.
4) Drawings shall be provided on a minimum of 24" x 36" size sht. with the text hgt. of 1/8" minimum. Structural engineer shall seal and sign the drawings submitted.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/04/2006 DELMA ROBEY OUT TO CUSTOMER Completed
10/04/2006 SUE REEVES REJECT SHELF Completed