Permit Number: T06CM01972
Parcel: 133231340

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T06CM01972
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2006 GBONILL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
05/24/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide manufacturer's data for the proposed split
system, including the total amount of refrigerant
in the system.
2. Show that the HVAC system for room 22 complies
with Section 1104.2, IMC 2003.
3. Provide load calculations to justify the capacity
of the proposed HVAC system for room 22. Reference
Section 803.3.1, IMC 2003.
4. Provide mounting details for the HVAC equipment
and show that the installation of the air handler
and condensing unit does not adversely affect
the building structure.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/24/2006 GBONILL1 OUT TO CUSTOMER Completed