Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T06CM01972
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/24/2006 | GBONILL1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 05/24/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide manufacturer's data for the proposed split system, including the total amount of refrigerant in the system. 2. Show that the HVAC system for room 22 complies with Section 1104.2, IMC 2003. 3. Provide load calculations to justify the capacity of the proposed HVAC system for room 22. Reference Section 803.3.1, IMC 2003. 4. Provide mounting details for the HVAC equipment and show that the installation of the air handler and condensing unit does not adversely affect the building structure. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/24/2006 | GBONILL1 | OUT TO CUSTOMER | Completed |