Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T06CM01972
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/19/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM01972 5/19/06 Provide manufacturer's cut sheets for new units, including all electrical data, specifications, and requirements. Please note that a 50 AF in the field is backed up by a 40A CB at the panel. |
05/19/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide manufacturer's data for the proposed split system, including the total amount of refrigerant in the system. 2. Show that the HVAC system for room 22 complies with Section 1104.2, IMC 2003. 3. Revise the termination of the secondary condensate drain to discharge in a conspicuous point of disposal. Reference Section 307.2.3 (2), IMC 2003. 4. Provide load calculations to justify the capacity of the proposed HVAC system for room 22. Reference Section 803.3.1, IMC 2003. 5. Show that the ventilation of room 22 complies with the requirements of Section 403.3, IMC 2003. 6. Provide mounting details for the HVAC equipment and show that the installation of the air handler and condensing unit does not adversely affect the building structure. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/24/2006 | ADRIANNE OLIVO | OUT TO CUSTOMER | Completed |