Permit Number: T06CM01972
Parcel: 133231340

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T06CM01972
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM01972 5/19/06

Provide manufacturer's cut sheets for new units, including all electrical data, specifications, and requirements. Please note that a 50 AF in the field is backed up by a 40A CB at the panel.
05/19/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide manufacturer's data for the proposed split system, including the total amount of refrigerant in the system.
2. Show that the HVAC system for room 22 complies with Section 1104.2, IMC 2003.
3. Revise the termination of the secondary condensate drain to discharge in a conspicuous point of disposal. Reference Section 307.2.3 (2), IMC 2003.
4. Provide load calculations to justify the capacity of the proposed HVAC system for room 22. Reference Section 803.3.1, IMC 2003.
5. Show that the ventilation of room 22 complies with the requirements of Section 403.3, IMC 2003.
6. Provide mounting details for the HVAC equipment and show that the installation of the air handler and condensing unit does not adversely affect the building structure.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/24/2006 ADRIANNE OLIVO OUT TO CUSTOMER Completed