04/10/2006 MARTIN BROWN FIRE REVIEW Approved
04/25/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 4/27/06
ACTIVITY NUMBER: T06CM01959
PROJECT NAME: Photovoltaic System
PROJECT ADDRESS: 126 E. Limberlost Dr., Ste 100
ARCHITECT / ENGINEER: Schneider & Assoc.
PROJECT REVIEWER: Christy Foreman


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Provide detail of installation of panels as specified on sht. 2 of structural calculations on drawing S2.2.4.

2) Provide accurate cost / valuation for installation of panels and invertor. Include labor and material without discounts from TEP.
05/03/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Provide greater detail on the Outdoor Closet/Shed in which the Inverter is to be mounted. Need such information as location of door/entrance.
2. Installation in closet violates the basic rule in NEC 690.14 (C), which requires the photovoltaic disconnecting means to be located nearest the point of entrance of the system conductors. However, a new Exception in the 2005 Code allows this in the case where such system conductors are contained in metal raceways from the point of penetration of the surface of the building to the first readily accessible disconnecting means. Electrical Plans Examiner is willing to consider this. Please see NEC 690.14 and 690.31 (E) in the 2005 Code.
3. Please provide exact wording and specifications for the plaques required by NEC 690.56 (B) and 230.2 (E).
4. Plan view does not correspond to line diagram.
5. Specify that all equipment, including enclosures and terminations, shall be listed by an Independent Testing Laboratory.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/08/2006 AMERY KLAPPERT OUT TO CUSTOMER Completed
05/08/2006 SUE REEVES REJECT SHELF Completed