Review Details: COMMERCIAL TI

Permit Number - T06CM01938
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2006 GERRY KOZIOL WWM REVIEW Approved
04/21/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) CLARIFY SEPARATED USE WALL. OCCUPANCY OF TENANT NEXT DOOR. DESIGNATE ON DRAWINGS THE HR RATING OF WALL.
2) CLARIFY WITH STRUCTURAL CALCULATIONS THAT EXISTING STRUCTURE CAN CARRY HVAC EQUIPMENT. APPROXIMATE TOTAL OF 850 LBS.
3) APPEARS THAT OCCUPANT LOAD IS INACCURATE THERE IS NO DESIGNATED STORAGE SPACE. IT APPEAR TWO EXITS WILL BE REQUIRED FOR OCCUPANT LOAD.
4) IT APPEARS NEW RESTROOMS ARE NOT PER ANSI A117.1 2003. PROVIDE CLEAR FLOOR SPACE FOR THE WATER CLOSETS.
5) CLARIFY THAT THERE IS A SALES COUNTER AND IT MEETS ANSI A117.1 2003 SECTION 904.3.
04/21/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/21/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Section 804.4, IECC 2003 requires insulation on the first 8 feet of the SUPPLY and discharge piping if the specified water heater is not supplied with integral heat traps.
2. Provide the listing requirements and applicable standards for the owner-supplied water distillation unit.