Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM01938
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/11/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
04/11/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
04/11/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) IT APPEARS THAT THIS IS A2 OCCUPANCY. IF THIS IS MERCANTILE THE SEATING NEEDS TO BE REMOVED AND CLARIFICATION OF FUNCTIONS AT EACH MILLWORK LOCATION. CLARIFY / JUSTIFY FUNCTION OF KITCHEN. 2) JUSTIFY / CLARIFY SEPARATED / NON-SEPARATED USE. 3) IF THIS IS A CHANGE OF OCCUPANCY IT WILL NEED TO BE SUBMITTED FOR REVIEW. |
04/18/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Justify the use of an Ev = 1.0 (cooling only) for the ventilation calculations. 2. Provide ventilation for the break room. |
04/18/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Include the humidifier requirements when determining the total water demand. Provide listing information for the distillation unit. 2. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003. 3. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference Section 804.4, IECC 2003. 4. If the specified water heater is not supplied with integral heat traps, provide 0.5" of insulation with a maximum conductivity of 0.27 btu per inch/h °F on the first 8 feet of supply and discharge piping. Reference Section 804.4, IECC 2003. |
04/18/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/18/2006 | TERRY STEVENS | ZONING | REVIEW | Approved | |
04/21/2006 | AKLAPPE1 | WWM | REVIEW | Needs Review | |
04/21/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06CM01938 4/11/06 1. Provide available fault current at service, fault calculations, and fault current rating of new panel. 2. Water Heater is on Ckt A-22,24. Please correct this on Power Plan. 3. It appears that Panel A has 119A, not 1178A. Please correct this on the panel schedule. |