Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM01938
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM01938
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2006 MARTIN BROWN FIRE REVIEW Approved
04/11/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
04/11/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) IT APPEARS THAT THIS IS A2 OCCUPANCY. IF THIS IS MERCANTILE THE SEATING NEEDS TO BE REMOVED AND CLARIFICATION OF FUNCTIONS AT EACH MILLWORK LOCATION. CLARIFY / JUSTIFY FUNCTION OF KITCHEN.
2) JUSTIFY / CLARIFY SEPARATED / NON-SEPARATED USE.
3) IF THIS IS A CHANGE OF OCCUPANCY IT WILL NEED TO BE SUBMITTED FOR REVIEW.
04/18/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Justify the use of an Ev = 1.0 (cooling only) for the ventilation calculations.
2. Provide ventilation for the break room.
04/18/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Include the humidifier requirements when determining the total water demand. Provide listing information for the distillation unit.
2. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
3. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference Section 804.4, IECC 2003.
4. If the specified water heater is not supplied with integral heat traps, provide 0.5" of insulation with a maximum conductivity of 0.27 btu per inch/h °F on the first 8 feet of supply and discharge piping. Reference Section 804.4, IECC 2003.
04/18/2006 ROBERT SHERRY WATER REVIEW Approved
04/18/2006 TERRY STEVENS ZONING REVIEW Approved
04/21/2006 AKLAPPE1 WWM REVIEW Needs Review
04/21/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM01938 4/11/06

1. Provide available fault current at service, fault calculations, and fault current rating of new panel.
2. Water Heater is on Ckt A-22,24. Please correct this on Power Plan.
3. It appears that Panel A has 119A, not 1178A. Please correct this on the panel schedule.