Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM01919
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/03/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the sizes of the water pipes to cordinate with the submitted water pressure calculations. 2. Limit the length of trap arms for the foot spas per Secton 1002.2, UPC 2003. 3. Revise the drain/vent piping for both P-3 fixtures to provide a vent for the traps. 4. Provide the listing information for the hair screens (for P-3) and for the foot spas. 5. Provide backflow protection for the foot spas. |
| 07/03/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Determine the actual supply flow for the existing air conditioner (1600 CFM or 1975CFM). 2. Provide ventilation to the break room. 3. Revise the ventilation calculations to account for a common supply for different areas. Reference Section 403.3.2, IMC 2003. 4. Provide exhaust for the nail stations. Reference Footnote b, Table 403.3, IMC 2003. |
| 07/05/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06CM01919 7/3/06 Provide fault calculations for New Panel A. It is not permissable to use fuse let through data to attenuate fault current for panels. |
| 07/06/2006 | AOLIVO1 | WWM | REVIEW | Needs Review | |
| 07/06/2006 | AOLIVO1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |