Permit Number: T06CM01919
Parcel: 12110005D

Address:
2320 N SWAN RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM01919
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the sizes of the water pipes to cordinate with the submitted water pressure calculations.
2. Limit the length of trap arms for the foot spas per Secton 1002.2, UPC 2003.
3. Revise the drain/vent piping for both P-3 fixtures to provide a vent for the traps.
4. Provide the listing information for the hair screens (for P-3) and for the foot spas.
5. Provide backflow protection for the foot spas.
07/03/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Determine the actual supply flow for the existing air conditioner (1600 CFM or 1975CFM).
2. Provide ventilation to the break room.
3. Revise the ventilation calculations to account for a common supply for different areas. Reference Section 403.3.2, IMC 2003.
4. Provide exhaust for the nail stations. Reference Footnote b, Table 403.3, IMC 2003.
07/05/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM01919 7/3/06

Provide fault calculations for New Panel A. It is not permissable to use fuse let through data to attenuate fault current for panels.
07/06/2006 AOLIVO1 WWM REVIEW Needs Review
07/06/2006 AOLIVO1 BUILDING-COMMERCIAL REVIEW Needs Review