Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T06CM01919
Parcel: 12110005D

Address:
2320 N SWAN RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM01919
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2006 PATRICIA GEHLEN ZONING REVIEW Approved
04/18/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the ventilation calculations to take into account the different occupancy loads in the project space. Reference Sections 403.3 and 403.3.2, IMC 2003.
2. Include the nail salon area in the venntilation calculations.
04/18/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM01919 4/18/06

1. There are two circuits on the plans which are called A-18. According to the panel schedule they are for the signing, and according to the plans they are for receptacles. Please clarify.
2. Provide a circuit for the receptacle marked 2B.
3. Provide a circuit for EF-1 in the salon.
4. Show the overcurrent protection for the feeder for New Panel A.
5. If this is a change of occupancy, demonstrate compliance with the IECC.
6. Show the location of the electrical service on scaled drawing.
7. Provide fault calculations for the available fault current at New Panel A.
04/18/2006 ROBERT SHERRY WATER REVIEW Approved
04/18/2006 MARTIN BROWN FIRE REVIEW Approved
04/18/2006 LOREN MAKUS ENGINEERING REVIEW Approved
04/18/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a riser diagram for the water piping.
2. Show the proposed locations of the RPBP's for the pedi-cures and show to where they will drain.
3. Clarify the nature of P-3.
4. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference Section 804.4, IECC 2003.
07/03/2006 GBONILL1 WWM REVIEW Needs Review
07/03/2006 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review