Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM01919
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/18/2006 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
04/18/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the ventilation calculations to take into account the different occupancy loads in the project space. Reference Sections 403.3 and 403.3.2, IMC 2003. 2. Include the nail salon area in the venntilation calculations. |
04/18/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM01919 4/18/06 1. There are two circuits on the plans which are called A-18. According to the panel schedule they are for the signing, and according to the plans they are for receptacles. Please clarify. 2. Provide a circuit for the receptacle marked 2B. 3. Provide a circuit for EF-1 in the salon. 4. Show the overcurrent protection for the feeder for New Panel A. 5. If this is a change of occupancy, demonstrate compliance with the IECC. 6. Show the location of the electrical service on scaled drawing. 7. Provide fault calculations for the available fault current at New Panel A. |
04/18/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/18/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
04/18/2006 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
04/18/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a riser diagram for the water piping. 2. Show the proposed locations of the RPBP's for the pedi-cures and show to where they will drain. 3. Clarify the nature of P-3. 4. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference Section 804.4, IECC 2003. |
07/03/2006 | GBONILL1 | WWM | REVIEW | Needs Review | |
07/03/2006 | GBONILL1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |