Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T06CM01912
Parcel: 116275740

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM01912
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2006 TERRY STEVENS ZONING REVIEW Approved
07/18/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved