Permit Number: T06CM01891
Parcel: 12402047B

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T06CM01891
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/05/2007 RBROOKS1 ELECTRICAL-COMMERCIAL REVIEW Approved
09/05/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a letter from Tucson Water stating that they will allow the use of 5/8" meter to serve a demand of 15 GPM (Apartments 1-6) and 11 GPM (Apartments 7-8).
2. Revise the water sizing calculations for the use of PEX instead of copper and for individual water supplies instead of a common water supply.
3. Provide a water riser diagram for the supply for apartments 1-6.
09/05/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/20/2007 DELMA ROBEY APPROVAL SHELF Completed
09/20/2007 DELMA ROBEY OUT TO CUSTOMER Completed
09/20/2007 DELMA ROBEY REJECT SHELF Completed