Permit Number: T06CM01891
Parcel: 12402047B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM01891
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/26/2006 HEATHER THRALL ZONING REVIEW Needs Review ZONING WILL REVIEW THE BUILDING PLAN AT THE COUNTER WITH THE ARCHITECT WHEN THE SITE PLAN COMES BACK IN FOR MINOR REVISIONS.
10/27/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Sign and date the seal on the design documents. Reference Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. The pressure-balanced tub and shower valves must conform to ASSE 1016 to comply with the requirements of Section 420.0, UPC 2003.
3. Provide cleanouts for units 1-6 that comply with the requirements of Sections 707.4 and 707.11, UPC 2003.
4. Coordinate the water riser diagrams for units 1-8 and the call-outs for the plumbing fixtures with the floor plans. Show how the piping relates to the water heater and where the unit piping connects to the building piping.
5. Provide cleanouts for units 7-8 that comply with the requirements of Sections 707.4 and 707.11, UPC 2003.
6. Correct the call-outs for the plumbing fixtures as shown on Detail 1/MP1.3.
7. Remove the valve between the expansion tank and the water heater. Reference Section 608.3, UPC 2003 with local amendments.
10/27/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Sign and date the seal on the design documents. Reference Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Clarify the notes for the fan coil unit access panel on the second floor mechanical plan for units 7 & 8.
11/06/2006 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
11/16/2006 JOSE ORTIZ ENGINEERING REVIEW Denied Building Permits will be approved when the Site Plan and Grading Plan have been approved.

If you have any questions you may contact me at 791-5640 ext.1191 or Jose.Ortiz@tucsonaz.gov
11/21/2006 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied PLEASE HAVE ARCHITECT SIGN HIS PLANS, ALSO STRUCTURAL ENGINEER NEEDS TO SIGN STRUCTURAL PAGES.

1) CLARIFY COMPLIANCE WITH ICC A117.1 (ANSI117.1) SECTION 1004.3.1 FOR ACCESSIBLE ROUTE TO BEDROOMS.
2)CLARIFY COMPLIANCE FOR CLEARANCE AT DOORS ON ACCESSIBLE ROUTE PER SECTION 404.2.3.1 OF ICC A117.1.
3) PROVIDE TRUSS SHOP DRAWINGS APPROVED BY A REGISTRANT WITH SUBMITTAL STAMP APPROVAL BY CITY OF TUCSON. MUST BE ISSUED PRIOR TO INSTALLATION.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/16/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
01/16/2007 SUE REEVES REJECT SHELF Completed