Permit Number: T06CM01891
Parcel: 12402047B

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T06CM01891
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/26/2006 HEATHER THRALL ZONING REVIEW Denied TO: Development Services Department Plans Coordination Office

FROM: Heather Thrall
Senior Planner

PROJECT: T06CM01891
1627 E. 1st Street, new apartments
Site plan

TRANSMITTAL DATE: June 14, 2006

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. (Per last review) Per DS 2-02.1.12, clarify pedestrian paths to each point of principal entry to the units of the building (excluding private patios). Clarify handicapped ramp slope width and truncated dome positions on ramps leading from right of way to site.
RESPONSE: Showed pedestrian access and ramps, truncated domes in areas requested (THANK YOU) except one. The handicapped ramp on site -near the site entry- leads handicapped access into the PAAL. This design is not safe and must be revised. Staff has been advised a sidewalk connection from private property sidewalks to city right of way sidewalks is required. Please connect the on site sidewalk to the city sidewalk in the right of way and remove the stated handicapped ramp altogether.

2. (Per last review/ this review) Per DS 2-02.2.2.A.2, provide the actual lot coverage calculation next to the maximum allowed noted.
RESPONSE: Stated the actual lot coverage proposed is 73%. Per the LUC, designator "P" for multi-family in the R-3 zone, the maximum allowed lot coverage is 70%. Lot coverage consists solely of vehicular use area and building footprint. I saw your calculations included sidewalk area, which can be removed from the calculation. Please review the math and ensure lot coverage does not exceed 70%.

3. I AM WILLING TO REVIEW THE REQUESTED CHANGES OVER THE COUNTER, RATHER THAN REQUIRING A RESUBMITTAL. Please contact me via email at Heather.Thrall@tucsonaz.gov or at 791-4541x1156 to set up a review time.


I ALSO NOTED A DSMR IS IN REQUEST FOR THE TRASH PICK UP. UNTIL THE DSMR IS PROCESSED AND APPROVED, ZONING MUST WAIT TO ACTUALLY APPROVE THE SITE PLAN. PLEASE SUBMIT THE DSMR TO THE CDRC OFFICE FOR PROCESSING.

If you have any questions about this transmittal, please call (520) 791-5608.

HCT C:\planning\site\DSD\T06CM01891 1627 e 1st 2nd.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan
10/26/2006 HEATHER THRALL ZONING HC SITE REVIEW Denied Please see zoning review comments.
11/01/2006 ANDREW CONNOR NPPO REVIEW Denied Submit the City of Tucson Application for Exception; include acceptable documentation, which clearly indicates that the project will not impact Protected Native Plants. Such documentation includes photographs of the site taken from all sides of the property. Photographs of the site are necessary for NPPO approval per DS 2-15.2.0.C
11/01/2006 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. All landscaping and screening must comply with the sight visibility requirements of Development Standard 3-01.0. Plant materials located within sight visibility triangles should consist of ground cover or low-growing vegetation of a species that will not grow higher than thirty (30) inches. Some species of Leucophyllum will typically grow in excess of 3 feet, Leucophylum candidum "Thunder Cloud" would be acceptable. Revise the landscape plan as necessary to remove vegetation or choose appropriate plant material that will not meet requirements within the SVT.

2. Submit the City of Tucson Application for Exception; include acceptable documentation, which clearly indicates that the project will not impact Protected Native Plants. Such documentation includes photographs of the site taken from all sides of the property. Photographs of the site are necessary for NPPO approval per DS 2-15.2.0.C
11/16/2006 JOSE ORTIZ ENGINEERING REVIEW Denied November 16, 2006
ACTIVITY NUMBER: T06CM01891
PROJECT NAME: 1st Street Apartments
PROJECT ADDRESS: 1627 E. 1st Street
PROJECT REVIEWER: Jose E. Ortiz PE, Civil Engineer
Second Review

Resubmittal required; The following items must be revised or added to the Site Plan, & Grading Plan.

SITE PLAN
1. Please include a response letter with the next submittal that states how all comments have been addressed. Include plans/redlines from previous plan submittal.

2. Sidewalks must be physically separated from any vehicular travel by means of curbing, grade separation, etc…, therefore curbing or another means of separation is required between the proposed sidewalk and the PAAL per D.S. 2-08.4.1. Revise cross section 1 on sheet C2.0 to reflect the physical separation.

3. The DSMR Case Number needs to be placed on the Site Plan for the Dumpster accessibility restriction.

4. Remove revision clouds. The revision clouds and revision numbers are not needed during plan review. The revision clouds/numbers are needed for plans that have been revised after approval.

5. On sheet C1.0 the Grading Plan Reference # is incorrect. The number should read T06BU00727.

GRADING PLAN
See T06BU00767 for Grading Plan Comments.

If you have any questions or would like to meet with me before your next submittal, you may contact me at 791-5640 ext.1191 or Jose.Ortiz@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
01/16/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
01/16/2007 SUE REEVES REJECT SHELF Completed