Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Minimum font size is 1/8".
2. Specify the long run from the last negative PV panel to the transition box. MC cable runs between panels, and the EMT runs have THHN, but this element is not defined.
3. Fronius Inverter Note #2 appears to have some incorrect values. Please check them against the values given on the 1-Line Diagram by the photovoltaic array, which appear to reflect the values provided in the panel specifications.
4. Fronius specifications call for a 15A circuit breaker on the AC side for maximum overcurrent protection. The 20A breaker specified in Inverter Note 3 exceeds this maximum.
5. Since the DC disconnect and the AC disconnect are located around the corner from and a certain distance from one another, please provide the placards required by NEC 690.56 (B) and 230.2 (E). Provide the exact wording on the plans.
6. Specify how may poles the DC disconnect is to have. Reference NEC 690.13.
7. Specify that the fuses on the DC side shall be DC rated.
8. Please provide cut sheets for the listed Transition Boxes, Row Boxes, and Pass Through Boxes.