Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T06CM01816
Parcel: 11446020E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM01816
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied S1. CLARIFY ACCESSIBILITY, PER 2003 IBC AND ANSI A117.1 - 2003 ed, FOR THE BUILDING AND SITE:
1. SHOW ON DRAWINGS WHERE 20% OF PROJECT VALUATION IS SPENT ON ACCESSIBLITY OR
2. ADDRESS REQUIREMENT FOR 2ND ACCESSIBLE TOILET FACILITY, BASED ON AN OCCUPANT LOAD OF 64+.
3. PROVIDE NOTE ON DRAWINGS BY ARCHITECT OF RECORD STATING FULL CONFORMANCE WITH 2003 IBC CHAPTERS 11 AND 34 AND ANSI A117.1 - 2003ed.
S2. PROVIDE COMPLETED CODE REVIEW CHECKLIST SIGNED BY ARCHITECT OF RECORD.
S3. PROVIDE STRUCTURAL CALCULATIONS SHOWING NEW ROOF LOADS ARE WITHIN STRUCTURAL CAPACITY OF ROOF STRUCTURE OR SHOW STRENGTHENING REQUIRED ON DRAWINGS.
S4. RESOLVE EXPIRED PERMITS:
1. T00CM05961.
2. T01CM01551.
3. T99BU01724.
S5. PROVIDE ARCHITECT'S SIGN-OFF ON DRAWING A-2.
S6. SHOW CONNECTION OF NEW SOFFITS, etc TO STRUCTURE ABOVE AND WITHIN THE SOFFIT WTITH FASTENER TYPE, SIZE,SPACING/NUMBER.
03/31/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
04/07/2006 CAGUILA1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
04/07/2006 CAGUILA1 MECHANICAL-COMMERCIAL REVIEW Needs Review
04/07/2006 TERRY STEVENS ZONING REVIEW Approved
04/07/2006 CAGUILA1 WWM REVIEW Needs Review
04/07/2006 CAGUILA1 PLUMBING-COMMERCIAL REVIEW Needs Review
04/07/2006 CAGUILA1 FIRE REVIEW Needs Review
04/10/2006 DROBEY1 WATER REVIEW Needs Review