Permit Number: T06CM01815
Parcel: 13219017F

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM01815
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2006 MARTIN BROWN FIRE REVIEW Approved
04/26/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied
04/26/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Minimum font size is 1/8".
2. Sheet E-1.1 Keyed Note 1. Registered Electrical Engineer shall determine extent and type of Classified Location for replacement of fuel pump, turbines, and sump pumps. Also for the dispenser, and specify conduit and conductor size and type, overcurrent protection size and type, and location of disconnect . This location shall be clearly diagrammed on the plans. Registered Electrical Engineer shall provide full and detailed Electrical Design. Shall not rely on Contractor to verify "integrity of hazardous area and update."
3. Call for seals in dispenser conduits. Reference NEC 514.9 (A) & (B).
4. Demonstrate compliance with NEC 514.13.
5. Sheets E-1 and E-2 in Electrical review set are addressed 501 W Irvington. Project address for this permit is 4881 S Campbell. Please provide plans for this address.
04/26/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T06CM01815 .. 4881 S CAMPBELL AVENUE .. REMODEL STORE AT ARCO AP/PM GAS STATION .. DGL .. 1ST REVIEW .. 4/26/06 ..

TRANSMIT PRIOR SUBMITTAL/S WITH NEXT SUBMITTAL.


S1. Provide completed Code Review Checklist ;
1. Local Amendments?
2. Allowable Area Calculation.
S2. Clarify, by complete annotation, site property lines, ref SP-1, per 1997 U.A.C. Section 302.1.
S3. Resolve Expired Permits at this address:
1. T98BU00903.
2. T99BU01622.
S4. Drawings shall be completed per approved City of Tucson code 2003 IBC. Clarify designation/s as the UBC is not Tucson's current code.
S5. Pima County Health Dept. approval of plans required before permit can be issued.
S6. Revise the font size used on the drawings to a minimum of 1/8 inch (all upper case).
Reference Section 302.3, Uniform Administrative Code, 1997.
S7. Keynote 1 on drawing. A-1 appears to be an exterior wall but on drawings it appears to be an interior wall provide appropriate revised detail/wall section.
S8. Clarify per IBC Chapter 34, by cost estimate on drawing C-1where 20% of the cost of construction is spent to improve accessibility, ie: 1. It appears restrooms do not have floor clearance or vertical grab bar per ANSI A117.1 2003ed, 2. Detail accessibility signage, as to location and information, per ANSI A117.1 Section 7, ref 02/A-2, 3. Provide ramps, landings and detectable warnings, per ANSI Section 4.
S9. Clarify Accessibility of new equipment and fixtures: sales counter, soda fountain, gondolas, etc, ref drawings A-1, A-2, and A-2-1, per ANSI A117.1-2003ed sections 7,8 and 9.
S10. Void or delete all details in the set of drawings which are not used on this Project.
S11. Show on drawings occupant load for each area of floor plan, per IBC Section10.
S12. Provide Structural Calculations and Details required to show new roof-mounted equipment will not overload the existing roof structure or how it will be strengthened to support the additional loads, including new hood and shaft.
S13. Detail and specify roof covering to accomplish a weatherproof roof, ref B and C/A5, also Exhaust fan mounting detail/M-2 as well as Vent through roof detail/P2, please address these weatherproofing details on the Architectural Drawings.
S14. Provide Structural Calculations and Connection details for the soffit to the structure above and fastening for the soffit itself, including fastener type, size spacing/number, ref Details 03,04/A-2, 02,03, 04 and 05/A-4 and for all options proposed.
S15. Clarify shaft fire-rating by copy of fire listing on drawings and conforming construction details for the shaft on the drawings.
S16. Provide Electrical Drawings that are correct for this Project/Address.

Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111.
05/01/2006 GERRY KOZIOL WWM REVIEW Denied needs 8th floor credit evaluation
05/03/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The applicable code for all commercial plumbing projects is the 2003 Uniform Plumbing Code with Local Amendments.
2. All plans require a minimum of 1/8" type, all uppercase. Reference Section 103.2.3, UPC 2003.
3. The drawings do not show the presence of a grease trap. Provide a food service exemption letter from Pima County Industrial Wastewater Control (520-579-5923) showing that a grease trap is not required.
05/03/2006 ROBERT SHERRY WATER REVIEW Approved
05/03/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. Clarify the nature of hood EH-1; is it new or existing? . Reference Section 106.3.1, IMC 2003.
3. All UL 710-listed hoods are intended for use with fire extinguishing systems. Is the proposed (existing?) hood equipped with a fire suppression system? Reference Section 106.3.1, IMC 2003.
4. How is make-up air for the hood being supplied? Reference Section 508.1, IMC 2003.
5. The hood schedule on sheet M-2 calls for 600 CFM but the exhaust hood calculations on M-1 call for 700 CFM. Please coordinate the drawings. Reference Section 106.3.1, IMC 2003.
6. Provide details to show that the Type II hood is supported from the building structure in accordance with Section 507.6, IMC 2003.
7. Provide listing information for the proposed exhaust fan, EF-1, that shows that the fan is suitable for the Type II hood. Reference Section 106.3.1, IMC 2003.
8. The minimum insulation for ducts located in unconditioned spaces within the building envelope is R-5 (installed). Reference Section 803.2.8, IECC 2003.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/17/2006 SUE REEVES APPROVAL SHELF Completed
05/17/2006 ADRIANNE OLIVO OUT TO CUSTOMER Completed