Permit Number: T06CM01797
Parcel: 12510016A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM01797
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2006 ROBERT SHERRY WATER REVIEW Approved
09/01/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the design of the pressure regulator installation to delete the non-valved bypass. Reference Section 608.2, UPC 2003.
2. Provide a shut off valve for the building water service
3. Provide an upper terminal cleanout for P2 located in the east restroom. Reference Section 707.4, UPC 2003.
4. The revised stack & riser diagrams show only a single 2" VTR. Provide additional venting capacity per Section 904.1, UPC 2003. (Note also that the revised design for the future restrooms will not allow the future lavatories to be wet vented through the water closet vents. See Table 10-1, UPC 2003.)
5. Coordinate the roof drain and overflow drain, as shown in detail 9/A6.0, with the roof drains and overflow drains that are specified on sheet P1.0.
6. Clarify how the roof overflow drains are to be terminated. Reference Section 103.2.3, UPC 2003.
7. Show the sizes of the building water meter and reduced pressure backflow preventor. Reference Section 103.2.3, UPC 2003.
09/01/2006 TERRY STEVENS ZONING REVIEW Denied 9-1-06

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. Zoning has reviewed the building plans but cannot approve them at this time. Zoning will re-review and approve the building plans on the next submittal providing the stamped and approved site plans are included with the building plan package.

2. Two copies of the approved and stamped site plan, landscape and NPPO plans must be included with building plans.
09/01/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/11/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
09/13/2006 PATRICIA GILBERT ENGINEERING REVIEW Denied An approved site plan is required prior to building plan approval.
09/22/2006 GERRY KOZIOL WWM REVIEW Denied needs to show location/method of connection to public sewer.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/28/2006 CINDY AGUILAR OUT TO CUSTOMER Completed
09/28/2006 SUE REEVES REJECT SHELF Completed