Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T06CM01797
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/26/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/31/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | Approved site plan is required prior to grading plan submittal. |
| 06/01/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The 2003 Uniform Plumbing Code (with local amendments) is the controlling code for the City of Tucson. 2. The maximum flow rates for plumbing fixtures shall be consistent with ARS Title 45, Chapter 1, Article 12. See text at: (http://www.azleg.state.az.us/ArizonaRevisedStatutes.asp). Reference Section 402.1, UPC 2003, as amended by the State of Arizona. 3. According to Tucson Water, the water service pressure range for the chosen meter location is 80 to 87 PSI. Provide a pressure regulator complete with an accessible strainer and with an integral pressure bypass. Reference Section 608.2, UPC 2003. 4. Provide upper terminal cleanouts for the two restrooms being installed. Reference Section 707.4, UPC 2003. 5. Provide a vent for the floor drains (stack & riser diagram no. 2). Reference Section 901.0, UPC 2003. 6. Provide strainers for the roof overflow drains (detail 9/A6.0) per Section 1105.2, UPC 2003. 7. Clarify how the roof overflow drains are to be terminated. Reference Section 103.2.3, UPC 2003. |
| 06/01/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Clarify how the restroom exhaust fans are to operate ("interlock with lights and ac units"). |
| 06/01/2006 | ROBERT SHERRY | WATER | REVIEW | Denied | Show the locations and sizes of the building water meter and reduced pressure backflow preventor. Reference Section 103.2.3, UPC 2003. |
| 06/02/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Please note that the City of Tucson now enforces the 2003 IECC, not the 2001, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.htm. Additionally, the calculations submitted do not need to include Fixtures A, B, or F. Reference 2003 IECC 805.5.2; this section only pertains to INTERIOR Lighting Power. 2. For all lighting poles greater than 20' in height, a Registered Structural Engineer shall seal the calculations for the pole and foundation. 3. Please eliminate the #2 G and the 2/0 GND on the line side of the service disconnect. Reference NEC 250.24 (B). 4. City of Tucson does not allow the use of current-limiting overcurrent devices to attenuate fault current available at panelboards. |
| 06/08/2006 | GERRY KOZIOL | WWM | REVIEW | Denied | needs to show location/method of connection to public sewer. |
| 06/20/2006 | TERRY STEVENS | ZONING | REVIEW | Denied | 06/20/06 Development Services Department Zoning Review Section Terry Stevens Lead Planner Comments: 1. Zoning has reviewed the building plans but cannot approve them at this time. Zoning will re-review and approve the building plans on the next submittal providing the stamped and approved site plans are included with the building plan package. 2. Two copies of the approved and stamped site plan, landscape and NPPO plans must be included with building plans. |
| 06/23/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approv-Cond |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/06/2006 | GBONILL1 | OUT TO CUSTOMER | Completed |
| 07/06/2006 | SUE REEVES | REJECT SHELF | Completed |