Review Details: COMMERCIAL NEW

Permit Number - T06CM01797
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/26/2006 MARTIN BROWN FIRE REVIEW Approved
05/31/2006 PATRICIA GILBERT ENGINEERING REVIEW Denied Approved site plan is required prior to grading plan submittal.
06/01/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The 2003 Uniform Plumbing Code (with local amendments) is the controlling code for the City of Tucson.
2. The maximum flow rates for plumbing fixtures shall be consistent with ARS Title 45, Chapter 1, Article 12. See text at: (http://www.azleg.state.az.us/ArizonaRevisedStatutes.asp). Reference Section 402.1, UPC 2003, as amended by the State of Arizona.
3. According to Tucson Water, the water service pressure range for the chosen meter location is 80 to 87 PSI. Provide a pressure regulator complete with an accessible strainer and with an integral pressure bypass. Reference Section 608.2, UPC 2003.
4. Provide upper terminal cleanouts for the two restrooms being installed. Reference Section 707.4, UPC 2003.
5. Provide a vent for the floor drains (stack & riser diagram no. 2). Reference Section 901.0, UPC 2003.
6. Provide strainers for the roof overflow drains (detail 9/A6.0) per Section 1105.2, UPC 2003.
7. Clarify how the roof overflow drains are to be terminated. Reference Section 103.2.3, UPC 2003.
06/01/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify how the restroom exhaust fans are to operate ("interlock with lights and ac units").
06/01/2006 ROBERT SHERRY WATER REVIEW Denied Show the locations and sizes of the building water meter and reduced pressure backflow preventor. Reference Section 103.2.3, UPC 2003.
06/02/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Please note that the City of Tucson now enforces the 2003 IECC, not the 2001, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.htm. Additionally, the calculations submitted do not need to include Fixtures A, B, or F. Reference 2003 IECC 805.5.2; this section only pertains to INTERIOR Lighting Power.
2. For all lighting poles greater than 20' in height, a Registered Structural Engineer shall seal the calculations for the pole and foundation.
3. Please eliminate the #2 G and the 2/0 GND on the line side of the service disconnect. Reference NEC 250.24 (B).
4. City of Tucson does not allow the use of current-limiting overcurrent devices to attenuate fault current available at panelboards.
06/08/2006 GERRY KOZIOL WWM REVIEW Denied needs to show location/method of connection to public sewer.
06/20/2006 TERRY STEVENS ZONING REVIEW Denied 06/20/06

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. Zoning has reviewed the building plans but cannot approve them at this time. Zoning will re-review and approve the building plans on the next submittal providing the stamped and approved site plans are included with the building plan package.

2. Two copies of the approved and stamped site plan, landscape and NPPO plans must be included with building plans.
06/23/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approv-Cond