Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T06CM01782
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/03/2006 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 04/07/2006 | BROWN & ASSOCIATES | 2ND PARTY REVIEW | REVIEW | Denied | Brown & Associates 177 N Church Avenue, Suite 311 Tucson, Arizona 85701 Office (520) 882-4735 Fax (520) 882-5412 1st - Review RESIDENTIAL PLAN REVIEW Client: City of Tucson Reviewer: Jake Hesselgesser Project: 2040 N. Norton Ave. #2 Permit #: T06CM01782 Date: April 6, 2006 Brown & Associates #: 85701-6217 _______________________________________________________________ 2003 International Residential Code, 2003 UPC with State Amendments, Outdoor Lighting Code; 2003 IBC applies for engineered structural designs. Residence Area: 1585 Exist S.F. Number of Floor Levels: 2 Garage Area: TBD S.F. Additional # of Elevation Options: 1 Porch/Stair/Deck Area: TBD S.F. Building Wall Construction: Rastra Block Basement Level Area: n/a S.F. Building Grade Floor Construction: S.O.G. Guest House Area: 1140 S.F. Building Roof Construction: Wood Guest House Construction: V-B Elevated Floor Construction: Wood Remodel Area: n/a S.F. NOTE: THE FOLLOWING ITEMS NEED TO BE CORRECTED PRIOR TO RESUBMITTING YOUR PLANS FOR APPROVAL. RETURN ALL SUBMITTAL PLANS AND DOCUMENTS WITH YOUR REVISED SUBMITTAL PLANS AND DOCUMENTS. . X Revise Plans for Compliance IRC Section R105.3.1 GENERAL REQUIREMENTS: X 1. On the first sheet of architectural plans provide a square footage summary for each of the following: residence area, garage, covered patios and porches, exterior decks and stairs. List all construction drawings that comprise the building plan submittal. R106, R108.3. X 2. There are several conflicting notes and details found on the plans (i.e.: water line size on site plan and plumbing plan, direction of section cuts, etc. Coordinate plan submittal and clarify construction documents. IRC R106.1.1. X 3. The location of structural foundations near ascending or descending slopes steeper than 1 vertical to 3-horizontal, shall be set-back and elevated as required. R403.1.7, R403.1.7.4 ARCHITECTURAL PLAN COMMENTS X 1. Locate on the plans, mark and identify the size, type and other requirements for all windows and emergency exit windows. IRC Section R303, R308, R310. X 2. Indicate the scale of each drawing found on the plans. IRC Section R106.1.1. X 3. Note and specify that the shower area and shower tub walls shall be finished with a nonabsorbent surface to a height of six feet above the floor. IRC Section 307.2. X 4. Specifically identify on the plans or elevations those glazing panes which must be tempered glazing. IRC Section R308.4. X 5. An attic access opening shall be provided to attic areas that exceed 30 square feet and have a vertical height of 30 inches. The rough-framed opening shall not be less than 22 inches by 30 inches and shall be located in a hallway or other readily accessible location. A 30-inch minimum unobstructed headroom in the attic space shall be provided at some point above the access opening. IRC Section R807.1. X 6. Openings between the garage and residence shall be equipped with solid wood doors not less than 1 3/8-inch thick, or shall be 20-minute fire-rated doors and shall be maintained self-closing and self-latching. The carport area as identified on the plans is a garage by definition of IRC Section R309. Amendment to IRC Section R309.1. X 7. There shall be no openings in the common wall between a garage and any sleeping room. The garage shall be separated from the residence and its attic area by not less than 1/2-inch gypsum board applied to the garage side. Garages beneath habitable rooms shall be separated from all habitable rooms above by not less than 5/8-inch Type X gypsum board or equivalent. Where the separation is a floor-ceiling assembly, the structure supporting the separation shall also be protected by not less than 1/2-inch gypsum board or equivalent. In buildings protected by an automatic fire sprinkler system, including the private garage, the separation shall be permitted to be limited to a minimum 1/2-inch gypsum board applied to the garage side. Amendment to IRC Section R309.1 and R309. X 8. Unless appropriately ventilated with mechanical equipment, all habitable rooms shall be provided with aggregate glazing area of not less than 8 percent of the floor area of such rooms. The minimum openable area to the outdoors shall be 4 percent of the floor area being ventilated. Identify the size and operation of all windows. IRC Section R303.1. X 9. Provide attic ventilation calculations for all concealed attic spaces; include required and provided net free ventilation area. Indicate the size, type, wire mesh and location of attic ventilation. Provide the following note, if applicable: "Where eave or cornice vents are installed insulation shall not block the free flow of air. A minimum of 1 inch space shall be provided between the insulation and roof sheathing at the location of the vent”. IRC Section R806. X 10. Indicate the effective code editions on the front sheet of the plans and revise code edition references throughout to be consistent with codes adopted by the City of Tucson. IRC Section R106.1.1. X 11. Clarify new and proposed construction. The carport is indicated as existing, however the plans show details and callouts for construction of the carport. Clarify and include all new areas in square footage calculation. IRC R106.1.1. ARCHITECTURAL BUILDING ELEVATION COMMENTS: X 1. Depict and specify all materials used - stucco, concrete block, glass block, siding, veneers, etc. and items projecting through roof or supported on the roof. IRC Section R703. X 2. Provide height dimensions for, roofline, windows, doors, top plates, finished floors and surrounding grade. Also indicate ceiling heights on plans. There are several discrepancies between cross sections and elevations. IRC Section R106. X 3. Provide exterior wall veneer anchoring method, backing and support. (ICBO Evaluation Report number if applicable). IRC Section R703.7.2, R703.7.4 X 4. For thin coat stucco systems over foam board, note and specify the ICBO Evaluation Report number, system name and manufacturer and show complete wall details. R104.9, R104.11 X 5. Specify required installation for the weather-resistant sheathing paper or other approved material. R703.2 ARCHITECTURAL BUILDING CROSS SECTION COMMENTS: X 1. Cross-sections shall be cross-referenced to the floor plan and structural plans and shall accurately depict the construction at the cross-section location. R106.1.1 X 2. Provide dimensions or otherwise indicate floor to floor height and height to top plate of 2nd floor. R106.1.1 X 3. Depict all materials used for construction of the roof including but not limited to substrates, underlayment, roof insulation and roof finish. R904, R905. ARCHITECTURAL ROOF PLAN COMMENTS: X 1. Provide complete roof plans indicating location of all equipment and openings therein. Note and specify a complete roofing assembly system including roof classification, type and grade of materials, valley and other flashing materials, underlayment, and installation requirements. R902, R903, R904, R905, R906 X 2. Provide ICBO Evaluation Report number and manufacturer for concrete or clay-type tile roofing or metal roofing system. Identify on the drawing the maximum installed tile weight (psf). R905.3, R301.4 X 3. Depict and show all roof slopes, size and materials for roof drains, downspouts, gutters, overflows and scuppers. R106.1.1, R903.4, UPC Appendix D. ARCHITECTURAL STAIR REQUIREMENTS: X 1. Provide details showing stair construction, connection details and stringer sizes. R311.5 X 2. The maximum riser height shall be 7 3/4 inches and minimum tread depth shall be 10 inches. IRC Section R311.5.3. X 3. The minimum headroom in all parts of the stairway shall be not less than 6 feet 8 inches measured vertically from the slope plane adjoining the tread nosing or from the floor surface of the landing or platform. IRC Section R311.5.2 X 4. Four or more stair risers shall have at least one handrail. Handrails shall be provided on at least one side of the stairs, be continuous the full length of the stairs, and have minimum and maximum heights of 34 inches and 38 inches, respectively, measured vertically from the nosing of the treads. The handgrip portion of handrails shall have a circular cross section of 1 1/4 inches minimum to 2 5/8 inches maximum; edges shall have a minimum radius of 1/8 inch. IRC Section R311.5.6 X 5. The minimum height of guards shall be not less than 36 inches. Openings in guards shall have intermediate rails or ornamental closures that do not allow passage of a sphere 4 inches in diameter. Indicate guardrail requirements on plans. IRC Section R312. MODEL ENERGY CODE COMMENTS X 1. Provide on the architectural drawings a calculation to determine the percentage of glazing in the gross area of the exterior walls. Calculations to verify compliance with the jurisdiction’s adopted Energy Conservation Code are required when the glazing area of a detached dwelling exceeds 15-percent of the gross area of the exterior walls. IRC Section N1101.2.1, N1102.1 X 2. Identify on the mechanical drawing the required insulation R-value for all HVAC ducts. IRC Section N1103.3 X 3. Identify on the mechanical drawing the required equipment efficiency performance rating. IRC Section N1103.1 X 4. Identify on the mechanical drawing the required insulation for mechanical systems piping. IRC Section N1103.5 X 5. Identify on the mechanical drawing the required HVAC system controls. IRC Section N1103.2 X 6. Identify on the water heater detail, the required water heater efficiency performance rating. IRC Section N1104.1 X 7. Identify on the window and door details/schedules the proposed U-values and solar heat gain coefficients. IRC Section N1102.1, N1102.1.3 X 8. All building joints, seams, penetrations and other sources of air leakage through the building thermal envelope shall be noted to be caulked, weather-stripped, wrapped or otherwise sealed to limit uncontrolled air movement. N1102.1.10 X 9. Recessed Type IC rated lighting fixtures shall be clearly noted and specified on the drawings. The construction surrounding a recessed lighting fixture installation that utilizes a non-IC rated fixture shall be depicted and shown completely on the drawings. See Electrical comment # 24 and 28. N1102.1.11 STRUCTURAL FOUNDATION PLAN COMMENTS: X 1. Note and specify soil treatment and other requirements for termite protection. IRC Section R319, R407.1. X 2. Note and specify the finish grades around the building lot indicating requirement for drainage of storm water away from the building foundation. IRC Section R401.3. X 3. City of Tucson IBC Amendment Section 1805.2 Depth of Footings – The amendment changed the first sentence to read as follows: “The minimum depth of footings below the undisturbed ground surface shall be 12-inches for 1000 psf allowable foundation pressure and minimum 18-inches for values of Table 1804.2” X 4. Areas that are likely to have expansive, compressible, shifting or other unknown soil characteristics, the building official shall determine whether to require a soil test to determine the soil’s characteristics at a particular location. This test shall be made by an approved agency using an approved method. R401.4 The owner should be aware that certain risks associated with building on unknown foundation soils may be mitigated by obtaining a bona fide soils report by a qualified registrant engineer for the building site. X 5. The area of floor used for parking of automobiles or other vehicles shall be sloped toward the main vehicle entry doorway. IRC Sec. R309.3. X 6. The proposed structure does not meet the prescriptive design requirements of IRC Section R404.4. Provide structural engineering calculations sealed, signed and dated by an Arizona Registrant. The registrant shall also seal, sign and date the plans. X 7. Indicate requirements for connection of new foundation to existing foundation. Special inspection is required for anchors in hardened concrete and Rastra Block. IBC Section 1704. STRUCTURAL FRAMING PLAN COMMENTS: X 1. Provide complete floor and roof framing plans showing girders, beams, joists, rafters, material sizes, spacings, fasteners, spans, and plan dimensions for structural frame members. Identify all post sizes including jack and king studs. IRC Section R106.1.1 X 2. Note on the plan that all wood materials shall bear an approved grading stamp. R502.1, R602.1, R802.1 X 3. Specify all structural material types, species, grades, etc. and depict the construction of all walls, roofs, floors and braced/shear walls. Wood stud and steel stud construction shall be shown to comply with the prescriptive requirements of applicable IRC Sections or the components shall be designed by an Arizona Registrant. Wood, steel, masonry and concrete components shall comply with prescriptive/empirical design requirements of IRC Sections or shall be designed by an Arizona Registrant. R301.1.3, R401, R501, R502.2, R505, R601, R602.10.10, R603, R604, R801, R1001, R1003 X 4. The proposed structure does not meet the prescriptive design requirements of IRC Section R404.4. Provide structural engineering calculations sealed, signed and dated by an Arizona Registrant. The registrant shall also seal, sign and date the plans. X 5. Rafters must be within the load and span limitations of IRC Table R802.5.1 (1) through (8). X 6. Floor joists must be within the load and span limitations of IRC Table R502.3.1 (1) and (2). X 7. Provide manufactures span charts for LVL’s. IRC R106.1. X 8. Specify design wind and seismic criteria and required floor live load, roof live load, attic live load and dead loads used for selection of joists, beams and girders. IRC Section R301. X 9. City of Tucson Amendment to Table R301.5 requires 40 psf for floor live load and 40 psf for storage or habitable attic floor. The bottom chord of attic trusses shall be designed for not less than 10 p.s.f. non-current live load or as may be required. X 10. Identify and specify structural sheathing for walls, floors and roofs. R503, R604, R803. X 11. Indicate the size and span of headers and lintels in all bearing and non-bearing walls. Indicate lintel requirements on plans. IRC Sections R602.7, R603.9, R606.9. X 12. Specify and show location for required framing hangers/connections used to attach trusses to girder trusses, walls, beams or other structural components. IRC Section R502.11, R802.10 & ANSI-TPI 1995, R104.11. X 13. Show framing around floor or roof openings and framing used to support roof mounted or attic mounted HVAC units. R016.1.1, R602.7, R802.9 MECHANICAL PLAN COMMENTS: X 1. Provide a notation on the mechanical drawing that: All ducts shall be sealed substantiately airtight by means of approved and listed tapes (UL 181A, UL-181B) , mastics, gaskets or other approved closure systems. IRC Section M1601.3.1 X 2. Provide combustion air for all liquid and solid fuel-burning appliances including size, type, and location of openings. IRC Chapter 1701. X 3. Provide detail to show termination requirements for combustion gas vents. G2427.6.5 PLUMBING PLAN COMMENTS X 1. Identify the total developed length of gas piping, BTUH gas demand of all appliances and provide suitable gas isometric showing the length of pipes (horizontal and vertical) to each appliance. R106.1.1, G2413; UPC 1217 X 2. Note that drainage piping serving fixtures which have flood level rims located below the elevation of the next upstream manhole cover of the public sewer shall be protected from backflow of sewage by a backwater valve. R106.1.1, P3008; UPC 710 X 3. Provide table of fixture unit counts for existing water supply piping and also indicate the meter size/available pressure. P2903.6, P2903.7; UPC 610 X 4. Show and specify requirements for sizing and installation of roof and overflow drains. R903.4.1; UPC Appendix D X 5. Designate the locations of water heaters. Indicate the location of the T and P relief line from the water heater to the exterior of the building. Note the T and P relief line to be full size steel pipe or hard drawn copper tubing extending to the exterior of the building and terminating in a downward position not more than 2 feet or less than 6 inches above grade. The T and P relief line shall not terminate over walkways, patios, carports or other similar areas. Show requirements for emergency drain pan and piping. P2803, P2801; UPC 505.3, UPC 510.7 ELECTRICAL PLAN COMMENTS: X 1. Provide smoke alarms in each sleeping room, outside each sleeping room in the immediate vicinity of the bedrooms and on each additional story of the dwelling, including basements and cellars. IRC Section 313. X 2. Smoke alarms shall receive their primary power from the building wiring with battery backup. Wiring shall be permanent without a disconnecting switch other than those required for overcurrent protection. IRC Section R313.2. X 3. Provide a detailed specific grounding electrode system (indicate size). IRC Section E3508. X 4. Provide bonding to the interior water piping and above ground portion of gas piping systems (indicate size). IRC Section E3509. X 5. Receptacles shall be installed so that no point along the floor line in any wall space is more than 6 feet, measured horizontally, from an outlet in that space, including any wall space 2 feet or more in width. IRC Section E3801.2.1. X 6. In kitchen and dining rooms, a receptacle shall be installed at each wall counter space 12 inches or wider so that no point along the wall is more than 24 inches from a receptacle outlet and shall be GFCI protected. IRC Section E3801.4. X 7. All 125-volt, single-phase, 15 and 20-ampere receptacles that serve countertop surfaces, and are located within 6 feet of the outside edge of a sink, wash basin, tub or shower shall be GFCI protected. IRC Section E3802.7 X 8. Fixtures, fittings, boxes and receptacles located in damp or wet locations shall be "listed" to be suitable for such location. IRC Sections E3805.11 E3902.8, E3902.9, E3903.8. X 9. Thermal insulation shall not be installed above a recessed luminaire or within 3-inches of the recessed luminaire's enclosure, wiring compartment or ballast except where such luminaire is identified (Type IC ) for contact with insulation. Coordinate with Model Energy comment # 9. E3904.9 OUTDOOR LIGHTING CODE: X 1. Provide catalog cuts of all outdoor lighting fixtures identifying fixture shielding or non shielding installation conditions and output lumens for each outdoor lighting fixture. X 2. Provide on the drawing appropriate tabular calculations that identify Outdoor Lighting Code site designation, total site area, allowable lumens per Table 5.1, conditions for installation of outdoor lighting fixture type, total lumens allowed at the site, maximum unshielded lumens at the site, and the actual installed lumens at the site for each fixture type. Requirements for this can be found on the jurisdiction’s web site. Sincerely, BROWN & ASSOCIATES Michael J. Brown, C.B.O. President MB:ns |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/10/2006 | DELMA ROBEY | OUT TO CUSTOMER | Completed |