Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T06CM01781
Parcel: 12810082B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM01781
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE WEIGHT FOR HOOD, DUCTWORK, AND EXHAUST FAN. PROVIDE STRUCTURAL CALCULATIONS JUSTIFYING THAT TRUSSES CAN CARRY THE ADDITIONAL LOAD.
COMMENTS ON RESPONSE PROVIDED.
2)CALCULATIONS DO NOT MATCH LOADS PROVIDED AND DETAILING AS PROVIDED.
3)ALSO NO LOAD WAS PROVIDED FOR BLACK IRON EXAUST DUCT.
4)ALSO ROOF FRAMING PLAN NEEDS TO BE PROVIDED WITH THE LOCATION OF EACH UNITS. ALSO SHOW AND INCLUDE IN CALCULATIONS THE EXISISTING EQUIPMENT / LOADS ON THE TRUSSES.
5)PER IMC 2003 507.6 WEIGHT OF PERSON WORKING ON EQUIPMENT NEEDS TO BE INCLUDED IN CALCULTIONS.
6) LOADS LISTED IN STRUCTURAL CALCS DO NOT MATCH WHAT IS LISTED ON M1.0.
7) NEED TO PULL LAST PERMIT TO VERIFY EXISTING LOADS THAT ALREADY EXIST ON ROOF FRAMING.
8) ROOF FRAMING LOCATION OF EQUIPMENT AND MECH. PLAN DO NOT MATCH. IT APPEARS HOOD, EXHAUST FAN, EVAP COOLER ARE ALL BEARING ON THE SAME JOISTS.
04/13/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
04/14/2006 ROBERT SHERRY WATER REVIEW Approved
04/14/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The provided listing information for the proposed Type I hood needs to noted as the basis for the hood design on the drawing. Reference Section 507.1 (1), IMC 2003. (Note that the provided listing information the exhaust fan does not match the scheduled unit.)
2. Comment not addressed. Provide information to show that the make up air for the kitchen hood complies with Section 508.1.1, IMC 2003.
3. The make up air provided by EC-1 is 180 CFM short of the exhaust flow rate. Provide information to show from where this additional make up is to be supplied and how it is to be interlocked with the operation of EF-1. Reference Section 508.1, IMC 2003.
4. The structural calculations for the hood support do not include the weight of the fan, roof curb, ventilated extension, hinged base, grease duct, and the possible weight of personnel working on or in the hood. Reference Section 507.6, IMC 2003.
05/01/2006 CAGUILA1 ENGINEERING REVIEW Needs Review
05/01/2006 CAGUILA1 ZONING REVIEW Needs Review
05/01/2006 CAGUILA1 WWM REVIEW Needs Review
05/01/2006 CAGUILA1 FIRE REVIEW Needs Review