Permit Number: T06CM01781
Parcel: 12810082B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM01781
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/30/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE WEIGHT FOR HOOD, DUCTWORK, AND EXHAUST FAN. PROVIDE STRUCTURAL CALCUALTIONS JUSTIFYING THAT TRUSSES CAN CARRY THE ADDITIONAL LOAD.
03/30/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide listing information (on the drawing) for the proposed Type I hood to show that it is listed for an exhaust airflow of 1000 CFM when used with medium-duty cooking appliance. Reference Section 507.1 (1), IMC 2003. (Note that the provided listing information does not match the scheduled unit.)
2. Revise the size of the grease ducts to provide a minimum velocity of 1500 feet per minute. Reference Section 506.3.4, IMC 2003.
3. Provide information to show that the make up air for the kitchen hood complies with Section 508.1.1, IMC 2003.
4. Provide information to show that the hood has clearances to combustibles per Section 507.9, IMC 2003
03/30/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/30/2006 ROBERT SHERRY WATER REVIEW Approved
03/31/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM01781 3/31/06

Mechanical Engineer has specified 115V equipment. Electrical has provided 208V power. Please coordinate with Mechanical and clarify.
04/13/2006 CAGUILA1 WWM REVIEW Needs Review
04/13/2006 CAGUILA1 ZONING REVIEW Needs Review
04/13/2006 CAGUILA1 ENGINEERING REVIEW Needs Review
04/13/2006 CAGUILA1 FIRE REVIEW Needs Review