Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2006 TERRY STEVENS ZONING REVIEW Approved
03/31/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/31/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
03/31/2006 ROBERT SHERRY WATER REVIEW Approved
03/31/2006 MARTIN BROWN FIRE REVIEW Approved
03/31/2006 RSHERRY1 WWM REVIEW Passed
03/31/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved See FUP # T06OT00897
05/24/2006 JWILLIA5 ELECTRICAL-COMMERCIAL REVIEW Passed
06/14/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE CALCULATIONS FOR SEPARATED USE. SEE SECTION 302.3.2 - THE BUILDING AREA SHALL BE SUCH THAT THE SUM OF THE RATIOS OF THE FLOOR AREA OF EACH USE DIVIDED BY THE ALLOWABLE AREA FOR EACH USE SHALL NOT EXCEED ONE. THE WHOLE BUILDING AT THIS TIME PER CITY INSPECTOR LERAY HANLEY IS IN NONCOMPLIANCE. SEVERAL FIRE BARRIERS HAVE BEEN REMOVED OR COMPROMISED. OTHER ALTERNATIVE IS TO PROVIDE FIRE WALL SEPARATION PER SECTION 705.
2) FOR SEPARATED USE THIS TENANT WILL NEED A 2 HR. FIRE EACH SIDE OF TENANT SPACE. ON BLDG PLANS OCCUPANCIES NEED TO BE DESIGNATED.