Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL TI
Permit Number - T06CM01762
Review Name: COMMERCIAL TI
Review Status: Active
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/31/2006 | TERRY STEVENS | ZONING | REVIEW | Approved | |
03/31/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
03/31/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
03/31/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
03/31/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
03/31/2006 | RSHERRY1 | WWM | REVIEW | Passed | |
03/31/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | See FUP # T06OT00897 |
05/24/2006 | JWILLIA5 | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
06/14/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE CALCULATIONS FOR SEPARATED USE. SEE SECTION 302.3.2 - THE BUILDING AREA SHALL BE SUCH THAT THE SUM OF THE RATIOS OF THE FLOOR AREA OF EACH USE DIVIDED BY THE ALLOWABLE AREA FOR EACH USE SHALL NOT EXCEED ONE. THE WHOLE BUILDING AT THIS TIME PER CITY INSPECTOR LERAY HANLEY IS IN NONCOMPLIANCE. SEVERAL FIRE BARRIERS HAVE BEEN REMOVED OR COMPROMISED. OTHER ALTERNATIVE IS TO PROVIDE FIRE WALL SEPARATION PER SECTION 705. 2) FOR SEPARATED USE THIS TENANT WILL NEED A 2 HR. FIRE EACH SIDE OF TENANT SPACE. ON BLDG PLANS OCCUPANCIES NEED TO BE DESIGNATED. |