Permit Number: T06CM01755
Parcel: 14126006H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM01755
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T06CM01755 .. 10701 EAST MARY ANN CLEVELAND WAY .. CELLTOWER/ LIGHT POLE .. .. DGL .. 2nd REVIEW COMMENTS .. 7/24/06 ..

PROVIDE RESPONSE LETTER WITH RE-SUBMITTAL.
TRANSMIT PRIOR SUBMITTAL/S WITH NEXT SUBMITTAL.

S1. See prior comment S2. (S2. Provide darker copies of Structural Calculations for Monopole for review and record purposes.)
S2. See prior comment S3. (S3. Provide and detail on drawings T-Mobile Shelter fire rating at wall adjacent to Property Line, show location of fire-rated wall on site plan, provide fire listings and construction details on the drawings to accomplish the required fire rating, see IBC Sections 6 and 7.)
S3. Shop drawings will be reviewed after Project is approved for permit, see prior comment S5. (S5. Submit two sets of shop drawings and calculations, stamped and signed by an Arizona Registered engineer, shop drawings shall be reviewed by and bear the approval of the Engineer or Architect of Record prior to submission to the City of Tucson, Development Services Department for approval prior to erection for:
1. Lightpole.
2. Existing Lighting System.
3. Antennas.
4. T-Mobile Shelter.)
S4. See prior comment S6. (S6. Provide Inspection Program as required by the 1997 Uniform Administrative Code as amended and adopted by the City of Tucson, Section 302.5.)
S5 See prior comment S7. (S7. Provide Special Inspection as required by the 1997 Uniform Administrative Code as amended and adopted by the City of Tucson, Section 306:
1. Caissons.
2. Bolts in concrete.
3. High strength bolting.
4. Field welding.
5. Concrete.
6. Reinforcing.
7. Antenna mounting.
8. Structural Integrity of Re-used Lighting System.
9. Mounting of Re-used Lighting System.
10. Lightpole Installation.
11. Shotcrete.)


Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111, email at <Doug.Laakso@tucsonaz.gov.> or visit City of Tucson , DSD website : www.tucsonaz.gov/dsd.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/03/2006 CINDY AGUILAR OUT TO CUSTOMER Completed
08/03/2006 SUE REEVES REJECT SHELF Completed