Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T06CM01729
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/21/2006 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 05/10/2006 | DANIEL RUSCH | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN REVIEW COMMENTS for Activity # T06CM01729 Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, model energy and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. PAGE 1: 1. Sect detail note ½ doesn't indicate any moisture barrier. 2. Provide detail for moment connection @outrigger supporting facia 3. Please indicate bearing of headers over doors & windows. Lintel schedule indicates header length is the same as door & window openings. PAGE 2 1. Indicate method of grounding new sub-panel. 2. Indicate protection for sub-panel circuit in main panel. 3. Fan boxes labeled for use.E4001.6 4. AFCI BEDROOM CIRCUITS E3802.11 5. Indicate smoke detector in hall between new &existing bedrooms. 6. Laundry circuit must comply with E3603.3 (only serve receptacles in laundry area.) 7. Provide an equipment specification list including furnace and evap. Cooler. 8. Air intake openings shall be located a minimum of 2' below any vent or chimney, R303.4. Intake must also be 10' minimum (horizontally) from vents and plumbing vents. 9. Indicate dryer vent. If you have any questions, please contact your assigned plans examiner Daniel Rusch at 791-5550, extension 1113. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/22/2006 | AMERY KLAPPERT | OUT TO CUSTOMER | Completed |
| 06/22/2006 | GBONILL1 | REJECT SHELF | Completed |