Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2006 MADARA ENGINEERING 2ND PARTY REVIEW REVIEW Denied MADARA Engineering, Inc.
4545 E. Shea Blvd. Suite 207, Phoenix, AZ 85028, phone (602) 493-1963, fax (602) 493-1967

Date: May 8, 2006

To: Meyer Development
70 E. Florence Rd.
Tucson, AZ 85704

Project name: 1227 E. Blacklidge Dr.
Permit #: TO6-CM01728
Structure: 1 story SFD
Occupancy: R-3/U
Occupant load: 4
Construction Type: V-B
Area S.F.: 2408 SF Project number: 18-6011-02


The second submittal plans for the above referenced project are in the process of Architectural, Structural, Plumbing, Mechanical and Electrical plan review for compliance with the City of Tucson ordinances and applicable codes. Corrections required are noted below. All corrections must be made to the original drawings and new complete and revised sets resubmitted along with a written response to each of the items listed below to facilitate a shorter back-check time.

The scope of this review covers Architectural, Structural, Plumbing, Mechanical and Electrical review. These disciplines were checked only to the extent allowed by the documents provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

ARCHITECTURAL COMMENTS
Demonstrate compliance with City of Tucson lighting ordinance. Provide the calculation for allowed lumens versus provided.
Show water meter and building supply line location on Site plan as well as gas meter.
Opening between the garage and residence shall be equipped with solid wood doors not less than 1 3/8 inch thick, or shall be 20-minute fire rated doors and shall be maintained self-closing and self-latching. Amendment to IRC Section R309.1. Self latching requirement has not been indicated.
Glass in hazardous areas shall be safety glass. Specify on applicable floor plans and elevations. Ref. IRC Section 308.4. Address glazing at bath tub and glazing in doors.
For stucco systems over wood-frame construction with a slab-on-grade, provide a detail showing the required separation between the weep screed and the surface below (min. 4" above the earth). Ref. IRC Section R703.2.1.
Provide attic ventilation calculations for all concealed attic spaces; include required and provided net free ventilation area. Also, indicate the type and location of attic ventilation. Provide the following note, if applicable: “Where eave or cornice vents are installed insulation shall not block the free flow of air. A minimum of 1 inch space shall be provided between the insulation and roof sheathing at the location of the vent” (non-vented roof design may be used meeting the TEP guidelines as agreed by the Greater Tucson Jurisdictions). Ref. IRC Section R806. If using the 1 to 300 ratio on a flat roof then a 1 perm vapor barrier is required.

STRUCTURAL COMMENTS
Sheet 2
Complete/ indicate all braced wall panel locations. Specify the method of bracing to be used. Ref. IRC Section R602.10. Comments restated, see marked locations where four more panels type A will be required prior to comply with the Conventional framing requirements.

Sheet 4
Indicate the size and span of headers and lintels in all bearing and non-bearing walls. Ref. IRC Sections R602.7 and R606.9. Specify header in front of garage.

PLUMBING COMMENTS
Indicate length of pipe from meter to most remote fixture. Show water line to each fixture and their sizes. Clarify 1 ¼” cw pipe entering building then changing to ¾”.

MECHANICAL COMMENTS
Indicate the SHGC coefficient for glazing per IRC N1102.2 when using the prescriptive requirements of IRC Chapter 11.

ELECTRICAL COMMENTS
Revise panel schedule/ plan circuiting so that plans are indicating all branch circuits installed in dwelling unit bedrooms shall be protected by an arc-fault circuit interrupter(s). Ref. NEC Article 210-12(b), IRC Section E3802.11.
In Kitchen and Dining Rooms, a receptacle outlet shall be installed at each wall counter space 12 inches or wider so that no point along the wall is more than 24 inches from a receptacle outlet and shall be GFCI protected. Ref. IRC Section E3801.4.1. Clarify counters at right hand side of sink and of range.
Denote surface mounted incandescent light fixtures in clothes closets shall maintain 12 inches between the fixture and the nearest point of storage. Ref. IRC Section E3903.11.
Show a power supply for dishwasher/ disposal and range that is not on the 20amp small appliance circuit.

Should you have any inquires regarding this letter, please do not hesitate to contact the Plan reviewer at (602) 493-1963.
MADARA Engineering for the CITY OF TUCSON
By:
Michael Hundley
Vice-President
05/10/2006 GERRY KOZIOL WWM REVIEW Approved